Detail operations and configurations, Opening menu status – BayTech RPC Single-phase Conbined QS User Manual

Page 20

background image

RPC with or without Ethernet

19

Detail Operations and Configurations

Opening Menu Status

IMPORTANT: The Factory default serial communications parameters are 9600 bps, 8 data
bits, 1 stop bit, and no parity.

Use modem adapter (BayTech Part No. 25MRJ45MD-8) to connect an external modem. Use the
9FRJ45PC-1 adapter (or other applicable adapter) and the RJ08X007 crossed cable to connect the
serial port of your computer to the RJ-45 port labeled “EIA-232” on your RPC unit. With a proper
connection to the unit upon power-up or unit reset, the following initialization and Status menu will be
displayed except the number of outlets will be dependent on the specific RPC unit:

NOTE: Switch 1 and 2 are the circuit breakers, closed means the circuit breaker has tripped. If
you have the external temperature probes installed their temperature will also be listed.

NOTE: The user will see only those outlets assigned to them by the admin user.

NOTE: An RPC prompt with an even number that is one greater than your model number (i.e.
RPC3 + 1 = RPC4), signifies the firmware is shared with the non-Ethernet unit where the
Ethernet part of the firmware is turned off.

This board is a Universal RPC Controller
..........Uncompressing...done.

BAYTECH
For further information check:
http://www.baytech.net/

UNIT INITIALIZATION
Universal RPC hardware rev: 1.01 serial numbers: 3800024
colilo bootload rev 1.05.01
readHostConfig
USING FACTORY DEFAULT SSH KEYS
readSSLCert
Initializing SNMP agent
found rpc on 2 1
ý

Unit ID: RPC3ADE-20
-------------------------------------------------------------------------------
| Outlet | True RMS | Peak RMS | True RMS | Average | Volt- |
| Group | Current | Current | Voltage | Power | Amps |
-------------------------------------------------------------------------------
| Outlet 1-8 | 0.2 Amps | 0.2 Amps | 120.7 Volts | 23 Watts | 23 VA |
-------------------------------------------------------------------------------
Internal Temperature: 73.4 F

Switch 1: Open 2: Open

1)...Outlet 1 : On
2)...Outlet 2 : On
3)...Outlet 3 : On
4)...Outlet 4 : On
5)...Outlet 5 : On
6)...Outlet 6 : On
7)...Outlet 7 : On
8)...Outlet 8 : On

Type Help for a list of commands
RPC>