Quick start: combined rpc series – BayTech RPC Single-phase Conbined QS User Manual
Page 11
RPC with or without Ethernet
10
QUICK START: Combined RPC Series
by Bay Technical Associates
For those Administrators who have requested the bare minimum for this type of equipment, follow
these steps exactly. If this is a new unit shipped directly from Baytech, follow the steps. If this is a
previously own unit, perform a factory reset to clear out any users and passwords still in the unit.
Outlet Control:
1. Connect the 9FRJ45PC-4 or 9FRJ45PC-1 adapter to your PC.
2. Connect the supplied rollover flat cable RJ08X007 to the adapter and to the EIA232 serial port
on the Baytech RPC device.
3. Use terminal emulation software to access the unit, (i.e. Microsoft Hyper-terminal). Set the PC
serial port configuration to the following: 9600 bps, 8 data bits, 1stop bit and no parity. If
your device has a B/C switch near the EIA232 port, set it to ‘B’.
4. If you get only a blinking cursor Press ‘Enter’. If still only a blinking cursor, Type 5 semi-
colons (;), there is a one second delay before the menu is displayed.
5. You should get the Outlet Status menu (Figure 1). This is the outlet controller circuits. If you
get the Network Menu (Figure 7), select option 1, Outlet Control to get to the Outlet Status
menu.
6. Type config and press ‘Enter’. You should see a menu similar to (Figure 4).
7. Select number for the Manage Users option. You should see a menu similar to (Figure 5).
8. IMPORTANT NOTE: the first user added will be the ADMIN user. Type ‘A’ and press
‘Enter’. Type the name of the admin user. The name is case sensitive.
9. Select the user number. You should see the name of the user selected a menu similar to (Figure
6).
10. Select ‘Add Outlet(s)’ to add a few outlets (i.e. 1, 2, 4) and press ‘Enter’ or select ‘Add All
Outlet’. A ‘Y’ signifies the outlet has been assigned to the user.
11. Press ‘Enter’ You should see a menu similar to (Figure 5) with the user name. Repeat steps 7
thru 9 to add other users.
12. Once you have added the users press ‘Enter’ until you get back to the Outlet Status menu,
(Figure 1). Type ‘Exit’. With (Microsoft Hyper-terminal) pressing ‘Enter’ will reconnect to the
unit outlet controller and ask for a use name. If this does not happen close the terminal emulator
session and open it again.
13. Type the name of a user to log in. You should see a menu similar to (Figure 1). The user will
see only the outlets assigned to them.
14. At the prompt type ‘password’ and press ‘Enter’. You should see prompts similar to (Figure 3).
15. Enter the password for the user. Repeat steps 12 thru 14 to add or change the password of the
user.
At this point you have enough Outlet Control Configurations to operate this Baytech Device.
Continue to the Ethernet Controller Configuration.
Ethernet Controller Configuration:
Before continuing your System Administrator needs to tell you to use DHCP or give you an IP
Address, Subnet Address, and Gateway Address.
1. If this Baytech device has an Ethernet port, at the prompt of any menu type five Attention
Characters (factory default is the semi-colon, {;}). The Attention Character will not echo on the
screen. You should see a menu similar to (Figure 7).