Maintenance, Maintenance -43 – Basler Electric BE1-BPR User Manual
Page 95

9272000990 Rev J
BE1-BPR Functional Description
4-43
POSC Command
Purpose:
Reads or programs the number of oscillographic fault records saved.
Syntax:
POSC[=x]
Comments:
x=6, 8, 10, or 12 (default)
Area one, two, or three password access is required to change the maximum number of
oscillographic records.
POSC
Maximum number of oscillographic records
HMI Menu Branch: N/A
Parameter
Setting Range
Pre-Fault Cycles
Post-Fault
Cycles
Cycles Per
Record
x
6
4
36
40
8
4
26
30
10
4
20
24
12
4
16
20
POSC Command Examples:
1. Read the maximum number of fault records that the relay is able to record.
POSC
6
2. Configure the relay to record 30 cycles of oscillography data in each fault record.
POSC=8
Maintenance
Maintenance involves configuring and verifying essential features of the relay. These features may be
programmed through the front panel controls or through the communications ports. The following list of
these features includes the corresponding commands in parenthesis. LCD contrast cannot be adjusted
through the communications ports. Output contact testing cannot be performed through the HMI.
•
Time and date settings (TIME, DATE, PCLK)
•
Communication port settings (COM)
•
Password settings (PW)
•
Fault detector calibration settings (CAL, FREQ)
•
HMI liquid crystal display (LCD) contrast
•
Default HMI display screen (PDISPLAY)
•
Output contact testing (OUT)
•
Software version reporting (VER)
Examples of typical MAINTENANCE menu screens are shown below.
MAINTENANCE
menu screen
CAUTION
Changing the POSC command setting will delete all existing fault records stored
in RAM. Fault records can be downloaded and saved prior to making a POSC
command setting change. Section 4, Functional Description, Software Functional
Description, Oscillographic Data Acquisition provides information about using the
FLT command to download and save fault records.
MAINTENANCE