Fault log (enhanced relays only), Fault log listing, Fault log (enhanced relays only) -39 – Basler Electric BE1-BPR User Manual
Page 91

9272000990 Rev J
BE1-BPR Functional Description
4-39
Fault Log (Enhanced Relays Only)
The fault log provides information about recent events that generated oscillograph data records. A record
is generated when the TRIGGER command logic expression becomes true. Events are numbered from 1
to 255 and are accessed in reverse chronological order (last in, first out). The number of an oscillograph
record corresponds to the number of the fault log. After fault log number 255 is recorded, fault log
numbering automatically starts over at fault log number 1. When the fault memory becomes full, the
oldest record is overwritten by the latest record acquired.
A list of fault log records can be viewed through the HMI menu screens or through a communications port
using the FLOG command. Each fault log listing shows the fault number, fault time and date, and the
protective elements that were active at the time the fault occurred. Examples of HMI and ASCII fault log
listings follow.
Fault Log Listing
FAULT LOG
menu screen
129 08:33:22.751 02/22/07, 50 TARGETS=A,N
128 08:33:09.796 02/22/07, 50 TARGETS=A,N
127 19:34:48.467 01/30/07, 50 TARGETS=A,N
126 14:25:09.663 12/20/06, 50 TARGETS=A,N
125 12:26:41.653 11/25/06, 50 TARGETS=A,N
124 11:19:19.684 11/01/06, 50 TARGETS=A,N
123 11:19:15.176 11/01/06, 50 TARGETS=A,N
122 12:08:23.488 10/09/06, 50 TARGETS=A,N
121 00:00:22.758 09/18/06, 50 TARGETS=A,N
120 23:55:09.896 07/22/06, 50 TARGETS=A,N
119 18:34:58.367 07/03/06, 50 TARGETS=A,N
118 13:25:06.613 05/20/06, 50 TARGETS=A,N
Sub-screen 1
Sub-screen 2
Sub-screen 10
FLOG
Fault log information.
HMI Menu Branch: 5
Parameter
Range
Comments
#
0: clears all fault records
1-255: provides summary
information about any one
of 255 fault records
Entering FLOG with no parameter will provide a
dated listing of the fault records stored in
memory.
FLOG Command
Purpose:
Reads a listing of all fault records, reads summary information about any individual fault
record, or clears all fault records.
Syntax:
FLOG[#][=0]
Comments:
This function is available on enhanced BE1-BPR relays only. No access area password s
required to read or reset fault log data.
FLOG Command Example:
Read fault log 125.
FLOG125
FAULT LOG #125
DATE = 11/25/07
TIME = 12:26:41.653
LOGIC=BFL1
I (1-7) =0111000
T (1-6) =100000
F (1-3) =111
120 23:55 7/22
50 TARGETS: AN
129 8:33 2/22
50 TARGETS: AN
129 8:33 2/22
50 TARGETS: AN
FAULT LOG (FLOG)