BE1-BPR Functional Description

4-49

CAL

Calibration values

HMI Menu Branch: 5 (Standard), 6

(Enhanced)

Parameter

Parameter Selections

Comments

amps

1 ampere units:
2 (low range)
8 (high range) ∗
5 ampere units:
10 (low range)
40 (high range) ∗

After calibration, the calibration

results are reported as “CAL OK” or

“CAL FAIL ”.
Entering CAL by itself will return the

calibration values for each

calibration range and phase. The

calibration values represent the

number of A/D bits per ampere for

each current input.

High range values are to be used only with enhanced units.


CAL HMI Screen Example:

CAL Command
Purpose:

Read or change calibration values.

Syntax:

CAL[x][=]

Comments:

x = 1 (low range, 2 (high range)

Access area one password is required to make calibration changes.


CAL Command Example:
Read the relay calibration values.

CAL

CAL1A=140.766; CAL1B=141.110; CAL1C=143.237; CAL1N=141.543

CAL2A=7.076; CAL2B=7.070; CAL2C=7.083; CAL2N=7.064

FREQ

Power system frequency

HMI Menu Branch: 5 (Standard), 6

(Enhanced)

Parameter

Parameter Setting

Default

freq

50 or 60

60

FREQ HMI Screen Example:

FREQ Command
Purpose:

Reads or changes the nominal power system frequency information used by the relay.

Syntax:

FREQ[=]

Comments:

Access area password one is required to change the setting.


FREQ Command Examples:
1. Read the frequency setting.

FREQ

60
2. Change the frequency setting to 50 hertz.

FREQ=50

CAL FREQ

RANGE-1L/2H 60

CAL FREQ

RANGE-1L/2H 60