Breaker failure logic with reclosing (bf+79), Breaker failure logic with reclosing (bf+79) -19, Figure 5-11. bf+79 logic diagram – Basler Electric BE1-BPR User Manual
Page 125

9272000990 Rev J
BE1-BPR BESTlogic Programmable Logic
5-19
Breaker Failure Logic with Reclosing (BF+79)
Figure 5-11. BF+79 Logic Diagram
LN=BF+79
LI6=4,12
LOA=T4+O15 ∗
LO9=0
LF1=PI,1
LI7=4,12
LO1=T1O7+T2
LO10=0
LF2=NI,1
LR=1,O10,/I1,I6,O11 LO2=T1O7+T2F3
LO11=0
LF3=PI,2
LT1=D,O8,/O8
LO3=T1O7+T2F3
LO12=F3I1
LI1=4,12
LT2=D,I5,/I5
LO4=O14
LI2=4,12
LT3=0,0,0
LO5=O8
LI3=4,12
LT4=D,O6,/O6
LO6=/I1/I2
LI4=4,12
LT5=D,O12,/O12
LO7=F1+F2
LI5=4,12
LT6=0,0,0
LO8=I3+I4+I5
∗
The non-maskable alarms ORed with the programmable diagnostics to provide an alarm output.