Figure 5-7. bfl1e logic diagram – Basler Electric BE1-BPR User Manual
Page 120

5-14
BE1-BPR BESTlogic Programmable Logic
9272000990 Rev J
Breaker Failure Logic 1 for Enhanced Relays (BFL1E)
Figure 5-7. BFL1E Logic Diagram
LN=BFL1E
LI6=4,12
LOA=T4+O14+O15 ∗
LO9=0
LF1=PI,1
LI7=4,12
LO1=O3
LO10=0
LF2=NI,1
LR=0,0,0,0,0
LO2=O3
LO11=0
LF3=PI,2
LT1=D,O8,/O8
LO3=T1O7+F1T2+O1O7
LO12=F3I1
LI1=4,12
LT2=D,I6,/I6
LO4=T5
LI2=4,12
LT3=0,0,0
LO5=T3
LI3=4,12
LT4=D,O6,/O6
LO6=/I1/I2
LI4=4,12
LT5=D,O12,/O12
LO7=F1+F2
LI5=4,12
LT6=0,0,0
LO8=T3O11
∗
The non-maskable alarms ORed with the programmable diagnostics to provide an alarm output.