Introduction, Table b-1. communication commands, Appendix b • commands summary – Basler Electric BE1-BPR User Manual
Page 173

9272000990 Rev J
BE1-BPR Commands Summary
B-1
APPENDIX B • COMMANDS SUMMARY
INTRODUCTION
Table B-1 provides an alphabetical list of communication commands. Refer to Figures 4-2 and 4-3 of
Section 4, Functional Description, for HMI menu branch numbering and screen locations.
Table B-1. Communication Commands
∗
= Enhanced Relays Only
HMI Menu Branch
Command
Function
Standard
Models
Enhanced
Models
ACCESS[=
Read/change access area in order to
change settings.
N/A
N/A
BKRCON[=
∗
Read/change breaker contact data.
3
3
BKROPS[=<#operations>,<52a/b contact logic>]
Read/change breaker operations data.
3
3
BKRRES[=
Read/change breaker resistor data.
N/A
N/A
CAL[x[=
Read/change ADC channel calibration.
5
6
COM[x[=
Read/change the serial communications
protocol.
5
6
CT[P/N][=
Read/change the Phase or Neutral CT ratio.
N/A
N/A
DATE[=
Read/change the date.
5
6
DIAG[=0]
Read/reset diagnostic log information.
2
2
DLOG[p[=
∗
Read/change the contact duty log.
N/A
3
FLOG[x][=0]
∗
Read fault log or clear FLOG and FAULT
data.
N/A
5
FLT<#.
∗
Read COMTRADE report for fault
N/A
N/A
FREQ[=
Read/change power system frequency.
5
6
HELP/H or HELP/H
HELP/H returns information about using
HELP. HELP/H
specific command.
HELP1/H1 returns a complete list of
commands.
N/A
N/A
I[
Read phase current in primary units.
2
2
ID[=
Read/change relay ID number for polled
communications.
N/A
N/A
LF[x][=
Read/change logic for fault detector
operation.
N/A
N/A
LI[x][=
Read/change logic for contact inputs.
N/A
N/A
LINFO[
Read logics available or
equations.
N/A
N/A
LN[=
Read/change custom logic name.
1
1
LO[#[=
Read/change program operation for an
output.
N/A
N/A
LOGIC[=
Read/change the name of the active logic
scheme.
1
1
LR[=
Read/program the logical inputs to the
recloser function block.
N/A
N/A
LT[x[=
Read/change logic for timer/counter
operation.
N/A
N/A
OUT[x][=<1/0>/DISABLE]
Pulse output ON (1) OR OFF (0) for test.
N/A
N/A
PCLK[=[
Read/program date/time format.
N/A
N/A
PDIAG[=
Read/program diagnostic alarms as ON (1)
or OFF (0).
N/A
N/A
PDISPLAY[=
Read/program the default display screen.
N/A
N/A
PHOLD[=<#####>]
Read/program the 200 msec output hold
mask.
N/A
N/A