Output hold function, Relay status, Output hold function -25 – Basler Electric BE1-BPR User Manual
Page 77: Relay status -25

9272000990 Rev J
BE1-BPR Functional Description
4-25
Output Hold Function
Protection outputs will usually have a minimum hold time to ensure that the protective relay contact does
not interrupt the trip coil current and the breaker close output will stay closed until the recloser shows that
the breaker has closed. The PHOLD command provides a 200-millisecond output hold time that can be
enabled or disabled for each output.
PHOLD
Output hold timers
HMI Menu Branch: N/A
Parameter
Parameter Selections
Defaults
#####
0 = no minimum hold time
1 = 200 ms minimum hold time
Each digit of the PHOLD parameter
represents an output. The leftmost
digit represents OUT1. The right-
most digit represents OUT5.
Typically, the 200 millisecond hold
time will be enabled for all outputs
except those used for reclosing.
PHOLD Command
Purpose:
Read or program the output hold timer mask.
Syntax:
PHOLD [=<#####>]
Comments:
Access area password 1, 2, or 3 required to change settings. Default setting is 11111.
PHOLD Command Example:
Disable the minimum hold time for output 3. Enable the minimum hold time for outputs 1, 2, 4, and 5.
PHOLD=11011
Relay Status
For diagnostic purposes, the RELAY STATUS menu screen provides a means of checking the status of
the current inputs, contact sensing inputs, output contacts, recloser, and relay diagnostics. This informa-
tion can also be obtained using the STATUS, I, and DIAG commands.
Typical RELAY STATUS screens are shown below on the left. An example of a report obtained using the
STATUS command is shown below on the right.
RELAY STATUS
menu screen
IA=3.00KA; IB=3.00KA
IC=3.00KA; IN=0.00KA
I (1-7) = 0100000
T (1-6) = 000000
F (1-3) = 001
O (A,1-15) = 0000000000000000
RECLOSER RESET
BREAKER CLOSED
DIAG: 1 to 1 TIMER ALARM
Sub-screen 1 Input
and Output Contact
Status
Sub-screen 2
Primary Current
Metering Values
Sub-screen 3
Secondary Current
Metering Values
Sub-screen 4
Recloser Status
Sub-screen 5+
Diagnostic
Message Screen(s)
DIAG: NONE
RECLOSER RESET
Ia=2.13 Ib=2.13
Ic=2.13 In=0.00
IA=1.28K IB=1.28K
IC=1.28K IN=0.00K
I1234567 OA12345
0000000 000000
RELAY STATUS