Basler Electric BE1-BPR User Manual
Page 132

6-4
BE1-BPR Communications
9272000990 Rev J
The following procedure describes how relay settings can be read, modified, saved to a file, and uploaded
to BE1-BPR relays. Any commercially available communications software may be used. Instructions for
configuring Windows HyperTerminal® are provided in Appendix A, Terminal Emulation.
1. Obtain password access to area one and use the SHOWSET command to obtain a report of all relay
settings. Getting password access to area one before using the SHOWSET command will ensure that
all passwords are displayed in the settings report. If password access is not obtained, passwords will
be displayed as asterisks (********).
2. Once the settings are displayed, copy the settings to a text editor such as Microsoft
Notepad
.
3. Edit the settings by making changes and deletions where required. You should ensure that each
command is terminated with a carriage return or semicolon and that line length does not exceed 40
characters. An example of settings that were read using the SHOWSET command and then copied to
a text editor is shown below. Text and settings that must be removed prior to uploading are shown
shaded in gray. The
PRESS ANY KEY TO CONTINUE… message can be avoided by setting the page
mode at P0 in the BE1-BPR communication settings. This setting is recommended if your terminal
emulation software included a scroll buffer.
PW1=AREA1PW,B; PW2=AREA2PW,B; PW3=AREA3PW,B; PW4=AREA4PW,B
LN=USER
LF1=PI,1; LF2=NI,1; LF3=PI,2
LI1=4,12; LI2=4,12; LI3=4,12; LI4=4,12; LI5=4,12
LI6=4,12; LI7=4,12
LR=0,0,0,0,0
LT1=D,O8,/O8; LT2=D,O9,/O9; LT3=C,O10,/O10; LT4=D,O6,/O6; LT5=D,O12,/O12
LT6=0,0,0
LOA=T4+O15
LO1=O3
LO2=O3
LO3=T1O7+F1T2+O1O7
LO4=T5
LO5=T3
LO6=/I1/I2
LO7=F1+F2
LO8=T3O11
LO9=T3I6+T3I7
LO10=I6+I7+O11
LO11=I3+I4+I5
LO12=F3I1
LOGIC=USER
FREQ=60
ID=0
PU1=1.00; PU2=1.00; PU3=1.00,10
TD1= 20m; TD2= 20m; TD3= 20m; TD4= 20m; TD5= 20m
TD6= 20m
TD791= 111m; TD792= 111m; TD793= 111m; TD79R= 111m; TD79F= 111m
TD79M= 111m
CTP=1; CTN=1
PHOLD=11111
SNAME=5,SUBSTATION_1
PCLK=M,24
PDISPLAY=0,0
COM0=96008N1,A0,E0,H0,P0,X0
COM1=96008N1,A0,E0,H0,P0,X0
PTARGET=0011111,11110
TRIGGER=O5
PTLOG1=0,L,0m; PTLOG2=0,H,11m; PTLOG3=0,L,11m; PTLOG4=0,H,12m; PTLOG5=0,L,13m
PTLOG6=0,H,14m
PDIAG=00000000,00000000
BKRCON=0.000E+00,0,0
BKROPS=,I1
BKRRES=0,0,0.000E+00