Breaker failure logic 2 for standard relays (bfl2), Figure 5-5. bfl2 logic diagram – Basler Electric BE1-BPR User Manual
Page 118

5-12
BE1-BPR BESTlogic Programmable Logic
9272000990 Rev J
Breaker Failure Logic 2 for Standard Relays (BFL2)
Figure 5-5. BFL2 Logic Diagram
LN=BFL2
LI6=4,12
LOA=T4+O15 ∗
LO9=T3I6+T3I7
LF1=PI,1
LI7=4,12
LO1=O3
LO10=I6+I7+O11
LF2=NI,1
LR=0,0,0,0,0
LO2=O3
LO11=I3+I4+I5
LF3=PI,2
LT1=D,O8,/O8
LO3=T1O7+F1T2+O1O7
LO12=F3I1
LI1=4,12
LT2=D,O9,/O9
LO4=T5
LI2=4,12
LT3=C,O10,/O10
LO5=T3
LI3=4,12
LT4=D,O6,/O6
LO6=/I1/I2
LI4=4,12
LT5=D,O12,/O12
LO7=F1+F2
LI5=4,12
LT6=0,0,0
LO8=T3O11
∗
The non-maskable alarms ORed with the programmable diagnostics to provide an alarm output.