Radio Frequency Interference (RFI)
Field tested using a 5 W, hand-held transceiver operating at random frequencies centered around 144
MHz and 440 MHz, with the antenna located six inches from the relay in both horizontal and vertical
planes.
Temperature
Operating:
-40°C to +70°C (-40°F to +158°F)
Storage:
-40°C to +70°C (-40°F to +158°F)
Shock
Type tested to withstand 15 G in each of three mutually perpendicular planes, swept over the range of 10
to 500 Hz for a total of 6 sweeps; 15 minutes each sweep, without structural damage or degradation of
performance.
Vibration
Type tested to withstand 2 G in each of three mutually perpendicular planes, swept over the range of 10
to 500 Hz for a total of 6 sweeps; 15 minutes each sweep, without structural damage or degradation of
performance.
Gost-R Certification
Gost-R certified, No. POCC US.ME05.B03391; complies with the relevant standards of Gosstandart of
Russia. Issued by accredited certification body POCC RU.0001.11ME05.
Weight
12 lb (5.44 kg) maximum