Breaker failure logic 3 for standard relays (bfl3), Figure 5-6. bfl3 logic diagram – Basler Electric BE1-BPR User Manual
Page 119

9272000990 Rev J
BE1-BPR BESTlogic Programmable Logic
5-13
Breaker Failure Logic 3 for Standard Relays (BFL3)
Figure 5-6. BFL3 Logic Diagram
LN=BFL3
LI6=4,12
LOA=T4+O15 ∗
LO9=T3I6+T3I7+T3O9
LF1=PI,1
LI7=4,12
LO1=O3
LO10=I6+I7+O9+O11
LF2=NI,1
LR=0,0,0,0,0
LO2=O3
LO11=I3+I4+I5+O8
LF3=PI,2
LT1=D,O8,/O8
LO3=T1O7+F1T2+O1O7
LO12=F3I1
LI1=4,12
LT2=D,O9,/O9
LO4=T5
LI2=4,12
LT3=C,O10,/O10
LO5=T3
LI3=4,12
LT4=D,O6,/O6
LO6=/I1/I2
LI4=4,12
LT5=D,O12,/O12
LO7=F1+F2
LI5=4,12
LT6=0,0,0
LO8=T3O11
∗
The non-maskable alarms ORed with the programmable diagnostics to provide an alarm output.