Figure 4-7. reclosing logic circuit – Basler Electric BE1-BPR User Manual
Page 74

4-22
BE1-BPR Functional Description
9272000990 Rev J
Figure 4-7. Reclosing Logic Circuit
TD79
Reclose timer delays ∗
HMI Menu Branch: 2
Parameter
Unit of Measure
Range
Increment
Default
delay
milliseconds (m)
seconds (s)
cycles (c)
10 - 999 ms
1 - 600 seconds
1 - 36014 (60 Hz)
1 - 30000 (50 Hz)
1 ms
0.1 s (1-100 s)
1.0 s (100-600 s)
1 cy
TD791=50m
TD792=1.0s
TD793=5.0s
TD79R=120s
TD79F=0m
TD79M=0m
∗
All timer settings greater than or equal to 1 second are rounded to 0.1 second resolution.
TD79 HMI Screen Examples:
TD79 Command
Purpose:
Read or change recloser (79) time delay settings.
Syntax:
TD[x][=
Comments:
x = the number of the timer being read or changed where:
1 = TD791, the reclose shot 1 time delay
2 = TD792, the reclose shot 2 time delay
3 = TD793, the reclose shot 3 time delay
R = TD79R, the reset time delay
F = TD79F, the reclose fail time delay
M = TD79M, the maximum reclose operation time
Delay = the time delay in cycles, milliseconds, or seconds
A setting of zero disables a timer. An access area 1 or 2 password is required to change
settings.
TD79R 79F 79M
120m 0m 0m
TD791 792 793
50m 1.0s 5.0s