Fault recording, Model numbers, Specifications – Basler Electric BE1-BPR User Manual
Page 16: Fault recording -4, Model numbers -4, Specifications -4, Table 1-1. be1-bpr relays, 5 aac ct secondary, Table 1-2. be1-bpr relays, 1 aac ct secondary

1-4
BE1-BPR General Information
9272000990 Rev J
Fault Recording
Enhanced model BE1-BPR relays can also be configured to record and save digital fault data for all three
phases plus neutral (0 to 200 amperes) and the digital state of each input and output contact. Analog
waveforms are digitized by sampling the waveforms at a periodic rate and converting the measured
signals to digital values. When a fault occurs, the digital data is stored as a fault record. Multiple fault
records can be stored and recalled through the serial port by an operator. To display the fault waveform
for analysis, recalled data can be imported into a data base file and converted into a graph. Standard
programs that read and display ASCII data (in accordance with IEEE Standard Common Format for
Transient Data Exchange (COMTRADE) for Power Systems) can also be used. BESTView application
software provides a simple terminal interface to communicate with the relay, retrieve and display
COMTRADE oscillographic fault data, and provide a remote front panel interface. This software is not
required to communicate with the relay. However, it combines the functions of a number of separate
packages into one program that is optimized for the BE1-BPR relay. To order this software free of charge,
contact the Customer Service Department of the Power Systems Group, Basler Electric, and request the
BESTView Software Package.
MODEL NUMBERS
Tables 1-1 and 1-2 provide information for the nominal current input to the current transformers, part
number, options, mounting style, and operating power supply voltage. Standard BE1-BPR relays do not
have oscillography, fault records, contact duty logs, or two calibration levels (current metering is limited to
10 amperes).
Table 1-1. BE1-BPR Relays, 5 Aac CT Secondary
Part Number
Options
Mounting Style
IRIG
Power Supply
9272000300
Standard
19” Rack Mount
Yes
48/125 Vac/Vdc
9272000301
Standard
19” Rack Mount
Yes
125/250 Vac/Vdc
9272000302
Enhanced
19” Rack Mount
Yes
48/125 Vac/Vdc
9272000303
Enhanced
19” Rack Mount
Yes
125/250 Vac/Vdc
9272000309
Standard
Vertical Mount
Yes
48/125 Vac/Vdc
9272000310
Standard
Vertical Mount
Yes
125/250 Vac/Vdc
9272000311
Enhanced
Vertical Mount
Yes
48/125 Vac/Vdc
9272000312
Enhanced
Vertical Mount
Yes
125/250 Vac/Vdc
9272000328
Enhanced
Vertical Mount
Yes
48/125 Vac/Vdc
9272000329
Enhanced
19” Rack Mount
Yes
48/125 Vac/Vdc
9272000330
Enhanced
Vertical Mount
Yes
125/250 Vac/Vdc
9272000331
Enhanced
19” Rack Mount
Yes
125/250 Vac/Vdc
Table 1-2. BE1-BPR Relays, 1 Aac CT Secondary
Part Number
Options
Mounting Style
IRIG
Power Supply
9272000304
Standard
19” Rack Mount
Yes
48/125 Vac/Vdc
9272000305
Standard
19” Rack Mount
Yes
125/250 Vac/Vdc
9272000306
Enhanced
19” Rack Mount
Yes
48/125 Vac/Vdc
9272000307
Enhanced
19” Rack Mount
Yes
125/250 Vac/Vdc
SPECIFICATIONS
BE1-BPR Breaker Protection Relays have the following features and capabilities.