Figure 5-9. bfl3e logic diagram – Basler Electric BE1-BPR User Manual
Page 122

5-16
BE1-BPR BESTlogic Programmable Logic
9272000990 Rev J
Breaker Failure Logic 3 for Enhanced Relays (BFL3E)
Figure 5-9. BFL3E Logic Diagram
LN=BFL3E
LI6=4,12
LOA=T4+O14+O15 ∗
LO9=T3I6+T3O9
LF1=PI,1
LI7=4,12
LO1=O2
LO10=I6+O9+O11
LF2=NI,1
LR=0,0,0,0,0
LO2=T1O7+F1T2+O1O7
LO11=I3+I4+I5+O8
LF3=PI,2
LT1=D,O8,/O8
LO3=O13
LO12=F3I1
LI1=4,12
LT2=D,O9,/O9
LO4=T5
LI2=4,12
LT3=C,O10,/O10
LO5=T3
LI3=4,12
LT4=D,O6,/O6
LO6=/I1/I2
LI4=4,12
LT5=D,O12,/O12
LO7=F1+F2
LI5=4,12
LT6=0,0,0
LO8=T3O11
∗
The non-maskable alarms ORed with the programmable diagnostics to provide an alarm output.