Basler Electric BE1-BPR User Manual
Page 79

9272000990 Rev J
BE1-BPR Functional Description
4-27
I Command
Purpose:
Reads the primary current value of all or individual phases.
Syntax:
I[
Comments:
No access area password is required for reporting functions. Primary and secondary
current values are available through HMI menu branch 2.
I Command Examples:
1. Read Phase B current.
IB
3.23KA
2. Read all primary currents.
I
IA=3.23KA; IB=3.23KA; IC=3.23KA; IN=0.00KA
The DIAG command reads or resets any diagnostic alarms recorded by the relay.
DIAG
Diagnostic alarms
HMI Menu Branch: 2
Parameter
Description
Non-Maskable
Alarms
RAM ERROR: Static RAM read/write error
ROM ERROR: EPROM program memory checksum error
uP ERROR: Microprocessor self test error
EEPROM ERROR: EEPROM read/write error
EEDATA ERROR: EEPROM data checksum error
ADC ERROR: Analog to digital converter error
CALIBRATION ERROR: Relay not calibrated or calibration checksum error
POWER SUPPLY ERROR: Power supply out of tolerance
Maskable
Alarms
ALARM LOGIC (OA): Alarm logic (OA equation) was true
TIMER ALARM (TL): Timer alarm setting exceeded (refer to PTLOG
Command)
CONTACT DUTY ALM (DL): Contact duty maximum (DMAX) exceeded
(refer to BKRCON Command)
BKROP >1 SEC (BKR): Breaker operation (clearing) time was greater than 1
second
POWER RESET (RST): Power supply to microprocessor has been reset
CLOCK NOT SET (CLK): Real time clock not set
RECLOSE FAIL (RF): Reclose attempt failed
DIAG Command
Purpose:
Reads or resets diagnostic information.
Syntax:
DIAG[=0]
Comments:
No access area password is required to read or reset diagnostic information. Entering
DIAG=0 will reset all diagnostics that can be reset.
DIAG Command Example:
View any diagnostic alarms.
DIAG
TIMER ALARM