4 remote/local selection, Remote/local selection -9, Table 2-1 remote/local switch -9 – AMETEK M130 User Manual
Page 27: Table 2-2 remote mode power-on conditions -9

Sorensen Ethernet Option
Configuration
M130/M131 Programming Manual
2-9
2.2.4
R
EMOTE
/L
OCAL
S
ELECTION
Set the rear panel Remote/Local switch to select remote or local operation.
Table 2-1 Remote/Local Switch
Switch Position
Description
ON
Remote operation selected.*
OFF
Local operation selected.
Front panel control is enabled. Unit will switch to remote
operation upon the first Ethernet, or RS-232 command.
* In the ON position, the power hardware and Ethernet card initialize to the remote state
at power-on. In addition, front panel control remains disabled regardless of the state of
the REN line, or the GTL command. The special
SCPI command SYST[n]:LOCAL
Powering up in remote mode will result in the following operating conditions.
Table 2-2 Remote Mode Power-on Conditions
Condition
Default
Voltage
0 Volts (initial from factory power–on voltage);
otherwise, last value saved by SCPI command or by the
SAVE SETTINGS button in the Web Settings page.
See CAL:INIT:VOLT to change.
Current
0 Amps (initial from factory power–on current);
otherwise, last value saved by SCPI command or by the
SAVE SETTINGS button in the Web Settings page.
See CAL:INIT:CURR to change.
Soft Voltage Limit
Model maximum voltage
Soft Current Limit
Model maximum current
OVP Trip Voltage
Model maximum voltage +10% (initial from factory
power–on OVP); otherwise, last value saved by SCPI
command or by the SAVE SETTINGS button in the Web
Settings page.
See CAL:INIT:VOLT:PROT to change.
Delay
0.5 seconds
Foldback Protection
OFF
Output
ON
Hold
OFF
Unmask
NONE
Service Request Capability
OFF