Testing the safe pulse disabler, 8operation, 2 testing the safe pulse disabler – Pilz PMCprimo DriveP.01/AA0/4/0/0/208-480VAC User Manual
Page 90

8.2
Testing the safe pulse disabler
8
Operation
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
8-4
8.2
Testing the safe pulse disabler
8200
Testing the safe pulse disabler
8-
Sicherheit_Impulssperre_S1
The safety card meets the requirements of EN IEC 61508 up to SIL 3
and EN ISO 13849-1 up to PL e.
To achieve category SIL 3 or PL e, the operator must ensure that the
function of the safe pulse disabler is tested periodically, after 8 hours at
the latest, by triggering safety functions SS1 or STO:
By restarting after safety functions SS1 or STO have been triggered
as a condition of operation
or
By restarting after safety function SS1 has been triggered by the op-
erator
Betrieb_Impulssperre_Test
To test the safe pulse disabler, proceed as follows:
Betrieb_Neustart_S1
1. Switch input "SS1 Activate" or "SS1 SIL3/Reset" to 0 V
The safety card performs the safety function SS1 (Safe Stop 1) and
switches to a "STOP" condition. The "FAULT" LED flashes.
2. Switch input "SS1 Activate" or "SS1 SIL3/Reset" to 24 V.
The safety card switches to a "STARTUP" condition. The device and
the safe pulse disabler are tested. The "RUN" LED flashes.
The safety card switches to a "RUN" condition. The "RUN" LED is lit
continuously.
t
1
: At least 2 ms; time during which SS1 Activate or SS1 SIL3/Reset
must have a "0" signal
t
2
: Approx. 2 s, safety card's run-up time
SS1 Activate: Input for safety function SS1
SS1 SIL3/Reset: Input for SIL 3 and reset
STO Acknowledge: Output for feedback from safety function STO
"RUN" LED: System is ready
SS1 SIL3/Reset
1
0
1
0
1
0
1
0
SS1 Activate
STO Acknowledge
LED "RUN"
t2
t
t1
- PMCprimo DriveP.01/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/P/0/208-480VAC PMCprimo DriveP.03/AA0/4/0/0/208-480VAC PMCprimo DriveP.06/AA0/4/0/0/208-480VAC PMCprimo DriveP.24/ABB/4/0/0/208-480VAC PMCprimo DriveP.03/AB0/5/0/0/208-480VAC PMCprimo DriveP.06/AB0/2/0/0/208-480VAC PMCprimo DriveP.03/AB0/3/0/0/208-480VAC PMCprimo DriveP.06/AB0/3/0/0/208-480VAC PMCprimo DriveP.12/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/ABC/4/P/0/208-480VAC PMCprimo DriveP.12/AB0/3/0/0/208-480VAC PMCprimo DriveP.03/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/AAC/4/0/0/208-480VAC PMCprimo DriveP.24/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/2/0/0/208-480VAC PMCprotego D.01/000/0/0/2/208-480VAC PMCprotego D.03/000/0/0/2/208-480VAC PMCprotego D.06/000/0/0/2/208-480VAC PMCprotego D.12/000/0/0/2/208-480VAC PMCprotego D.24/000/0/0/2/208-480VAC PMCprotego D.12/000/0/P/2/208-480VAC PMCprotego D.72/000/0/0/2/208-480VAC PMCprotego D.24/000/0/P/2/208-480VAC PMCprotego D.48/000/0/0/2/208-480VAC PMCprotego D.01/200/0/0/2/208-480VAC PMCprotego D.01/100/0/0/2/208-480VAC PMCprotego D.01/010/0/0/2/208-480VAC PMCprotego D.06/010/0/0/2/208-480VAC PMCprotego D.06/100/0/0/2/208-480VAC PMCprotego D.06/200/0/0/2/208-480VAC PMCprotego D.03/010/0/0/2/208-480VAC PMCprotego D.03/200/0/0/2/208-480VAC PMCprotego D.03/100/0/0/2/208-480VAC PMCprotego D.12/010/0/0/2/208-480VAC PMCprotego D.24/200/0/P/2/208-480VAC PMCprotego D.12/200/0/0/2/208-480VAC PMCprotego D.12/100/0/0/2/208-480VAC PMCprotego D.12/010/0/P/2/208-480VAC PMCprotego D.12/200/0/P/2/208-480VAC PMCprotego D.24/100/0/P/2/208-480VAC PMCprotego D.24/010/0/P/2/208-480VAC PMCprotego D.12/100/0/P/2/208-480VAC PMCprotego D.24/200/0/0/2/208-480VAC PMCprotego D.24/100/0/0/2/208-480VAC PMCprotego D.24/010/0/0/2/208-480VAC PMCprotego S1 PMCprotego S2