Testing the safe pulse disabler

8

Operation

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

8-4

8.2

Testing the safe pulse disabler

8200

Testing the safe pulse disabler

8-

Sicherheit_Impulssperre_S1

The safety card meets the requirements of EN IEC 61508 up to SIL 3
and EN ISO 13849-1 up to PL e.

To achieve category SIL 3 or PL e, the operator must ensure that the
function of the safe pulse disabler is tested periodically, after 8 hours at
the latest, by triggering safety functions SS1 or STO:

By restarting after safety functions SS1 or STO have been triggered
as a condition of operation

or

By restarting after safety function SS1 has been triggered by the op-
erator

Betrieb_Impulssperre_Test

To test the safe pulse disabler, proceed as follows:

Betrieb_Neustart_S1

1. Switch input "SS1 Activate" or "SS1 SIL3/Reset" to 0 V

The safety card performs the safety function SS1 (Safe Stop 1) and
switches to a "STOP" condition. The "FAULT" LED flashes.

2. Switch input "SS1 Activate" or "SS1 SIL3/Reset" to 24 V.

The safety card switches to a "STARTUP" condition. The device and
the safe pulse disabler are tested. The "RUN" LED flashes.

The safety card switches to a "RUN" condition. The "RUN" LED is lit
continuously.

t

1

: At least 2 ms; time during which SS1 Activate or SS1 SIL3/Reset

must have a "0" signal

t

2

: Approx. 2 s, safety card's run-up time

SS1 Activate: Input for safety function SS1

SS1 SIL3/Reset: Input for SIL 3 and reset

STO Acknowledge: Output for feedback from safety function STO

"RUN" LED: System is ready

SS1 SIL3/Reset

1

0

1

0

1

0

1

0

SS1 Activate

STO Acknowledge

LED "RUN"

t2

t

t1