4.3.5
Safely limited speed - SLS
Safely limited speed - SLS
4-
Sicherheitsfunktion_SLS_Ueber
The safety function "safely limited speed" (SLS) monitors the drive to
check that it stays within a defined speed limit.
Sicherheitsfunktion_Sxx_Voraussetzung_S1
Prerequisites for normal operation:
Input "SS1 Activate" and "SS1 SIL3/Reset": "1" Signal (+24 VDC)
"Ready" output: "1" Signal (+24 VDC). The safety card is ready for op-
eration.
"STO Acknowledge" output: “0” Signal
Sicherheitsfunktion_SLS_Voraussetzung
Input "SLS Activate": "1" Signal (+24 VDC)
Sicherheitsfunktion_Sxx_Voraussetzung_SIL3
To achieve SIL3 or Ple: Connect the output "STO SIL3" to servo am-
plifier terminal X4A/ 3.
Sicherheitsfunktion_SLS_Ausloesung
Safety function is activated
By a 1/0 pulse edge at the input "SLS Activate".
Sicherheitsfunktion_SLS_Reaktion
Reaction:
SLS delay time starts
Once the SLS delay time has elapsed, the speed is monitored.
Output "SRA Acknowledge": "1" Signal
If the limit value is exceeded, safety function SS1 (E-STOP braking
ramp) is activated.
Sicherheitsfunktion_SLS_SSR_Toleranz
A tolerance range may also be set for the limit values used to monitor
the speed. This tolerance range modifies the set limit values. As a result,
one-off or periodic overshoots that exceed the limit values can be toler-
ated.
The following values can be set for the tolerance range:
Tolerance amount, which takes into account the size of the over-
shoots.
Tolerance time, which takes into account the length of the overshoots
Tolerence period that takes into account the variation period
Activate the tolerance range:
The tolerance range becomes active the first time the speed limit val-
ue is exceeded (see flowchart).
INFORMATION
See the Configurator's online help for details of how to set the
parameters for the tolerance range.
- PMCprimo DriveP.01/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/0/0/208-480VAC PMCprimo DriveP.12/AA0/4/P/0/208-480VAC PMCprimo DriveP.03/AA0/4/0/0/208-480VAC PMCprimo DriveP.06/AA0/4/0/0/208-480VAC PMCprimo DriveP.24/ABB/4/0/0/208-480VAC PMCprimo DriveP.03/AB0/5/0/0/208-480VAC PMCprimo DriveP.06/AB0/2/0/0/208-480VAC PMCprimo DriveP.03/AB0/3/0/0/208-480VAC PMCprimo DriveP.06/AB0/3/0/0/208-480VAC PMCprimo DriveP.12/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/ABC/4/P/0/208-480VAC PMCprimo DriveP.12/AB0/3/0/0/208-480VAC PMCprimo DriveP.03/AB0/2/0/0/208-480VAC PMCprimo DriveP.12/AAC/4/0/0/208-480VAC PMCprimo DriveP.24/AA0/5/0/0/208-480VAC PMCprimo DriveP.12/AA0/2/0/0/208-480VAC PMCprotego D.01/000/0/0/2/208-480VAC PMCprotego D.03/000/0/0/2/208-480VAC PMCprotego D.06/000/0/0/2/208-480VAC PMCprotego D.12/000/0/0/2/208-480VAC PMCprotego D.24/000/0/0/2/208-480VAC PMCprotego D.12/000/0/P/2/208-480VAC PMCprotego D.72/000/0/0/2/208-480VAC PMCprotego D.24/000/0/P/2/208-480VAC PMCprotego D.48/000/0/0/2/208-480VAC PMCprotego D.01/200/0/0/2/208-480VAC PMCprotego D.01/100/0/0/2/208-480VAC PMCprotego D.01/010/0/0/2/208-480VAC PMCprotego D.06/010/0/0/2/208-480VAC PMCprotego D.06/100/0/0/2/208-480VAC PMCprotego D.06/200/0/0/2/208-480VAC PMCprotego D.03/010/0/0/2/208-480VAC PMCprotego D.03/200/0/0/2/208-480VAC PMCprotego D.03/100/0/0/2/208-480VAC PMCprotego D.12/010/0/0/2/208-480VAC PMCprotego D.24/200/0/P/2/208-480VAC PMCprotego D.12/200/0/0/2/208-480VAC PMCprotego D.12/100/0/0/2/208-480VAC PMCprotego D.12/010/0/P/2/208-480VAC PMCprotego D.12/200/0/P/2/208-480VAC PMCprotego D.24/100/0/P/2/208-480VAC PMCprotego D.24/010/0/P/2/208-480VAC PMCprotego D.12/100/0/P/2/208-480VAC PMCprotego D.24/200/0/0/2/208-480VAC PMCprotego D.24/100/0/0/2/208-480VAC PMCprotego D.24/010/0/0/2/208-480VAC PMCprotego S1 PMCprotego S2