6-1

6.1

General wiring guidelines

6

Wiring

66000

Wiring

Wiring

6-

6.1

General wiring guidelines

6100

General wiring guidelines

6-

Verdr_Allgemein_S1_S2

Inputs

Appropriate wiring must be used to exclude short circuits between
the inputs or to a supply line!

Signal lines must be shielded.

Outputs

If short circuits occur between the cable from the output to the load
and a supply line, it will no longer be possible to switch off the load.

Possible remedy: Exclude the error by using separate multicore ca-
ble for supply voltages

Use appropriate wiring to exclude short circuits between the outputs!

Signal lines must be shielded.

The outputs do not need suppression for inductive loads.

Cable material

Use copper wiring.

Verdr_Leiterquerschnitte

Please note:

Cable cross sections for field connection terminals in mm

2

:

– Digital inputs/outputs, supply voltage: 0.5 (AWG20) ... 1.0

(AWG18), AEH without plastic collar, in accordance with DIN
46228/1

Verdr_Leitungslaengen

Max. cable lengths
– Supply voltage: Max. 30 m
– Digital inputs and outputs: Max. 30 m