XR500 Series Canadian Programming Guide

Digital Monitoring Products

67

APPENDIX

END - Select END to stop the Walk Test. When the Walk Test ends or a 20-minute

time-out expires, a final Sensor Reset occurs. The System Test End message is

sent to the receiver along with Verify and Fail messages for each zone under test.

Faulted zones then display on the keypad.

CKIN:XXX/ZZZ END

Trip Counter For DMP Wireless Check-in Test (WLS)

Displays the number of wireless zones that automatically communicate a supervision

check-in message.

• The number of zones that check in. (XXX in the example).
• The total number of wireless zones programmed for supervision that should

check in. (ZZZ in the example).

END - Select END to stop the Wireless Check-in Test. When the test ends or

a 20-minute time-out expires, normal wireless zone processing returns. If

all transmitters check-in, both numbers match within three (3) minutes. If a

transmitter has multiple zones (1101, 1114, etc.), all zones are included in the

counts. Failed wireless zones display on the keypad.

TEST END WARNING

Test End Warning

When five minutes remain on the 20 minute Walk Test timer, the keypad displays

TEST END WARNING. If no additional test zone trips occur, the test ends and a final

Sensor Reset automatically occurs. The System Test End message is sent to the

receiver along with Verify and Fail messages for each zone under Walk test. Faulted

zones then display on the keypad.
Note: Key fobs do not send failure messages in order to prevent functioning key fobs

that are not present at the time of the test from being reported as MISSING.

Failed Zones Display

ZONE: 10

-FAIL

For each zone that did not trip (failed) at least once during the Walk Test, all

keypads with matching Area Display programming display the zone name and number

and buzz for one second. Any selected (*FI *PN *SV) 24-hour zone that is faulted at

the end of the Walk Test displays a trouble condition for that zone regardless of the

message programmed for the open or short condition of the zone and a zone trouble

is sent to the receiver. Press the COMMAND key to display the next failed zone.
Note: For the Wireless Check-in Test, failed wireless zones display only on the

keypad. Zone Verify/Fail reports are not sent to the central station receiver for the

wireless check-in test.

Local Printer for Walk Test
When the Walk Test is completed, a Verify or Fail message for each zone tested prints to the local printer.

The Walk Test messages printing is enabled through Printer Reports programming.
Note: If ENHANCED ZONE TEST is selected as YES, the Verify messages are printed at the time the zone

trip occurs and not printed at the test end.

23.5 Keypad Speaker Operation

When using LCD Keypads, the panel provides distinct speaker tones from the keypad for Fire, Burglary,

Zone Monitor, and Prewarn events. The list below details the conditions under which the speaker is turned

on and off for each event.

Fire

On - Fire zone alarm and Bell Output or Fire Bell Output is ON.

Off - Alarm Silence.

Burglary

On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.

Off - Alarm Silence.

Zone Monitor On - One time only when a monitored zone is tripped.

Off - After one tone.

Prewarn

On - During Entry Delay.

Off - When Entry Delay expires.