3 pc modem, Pc modem – DMP Electronics DMP Command Processor Panel XR500 User Manual
Page 32
XR500 Series Canadian Programming Guide
Digital Monitoring Products
23
REMOTE OPTIONS
7.6
PC Modem
YES allows the panel to answer the telco link and connect with Remote Link through
the PC Modem at 2400 baud. NO disables PC Modem communication.
7.7
ALR RCVR NO YES
Alarm Receiver Authorization
Select YES to enable remote commands and programming to be accepted from the alarm
SCS-1R Receiver. The Remote Key option can also be required.
With YES selected, the panel requests the receiver key during its first communication
with the first SCS-1R Receiver. The panel retains this alarm receiver key in memory and
allows remote commands to be accepted from the alarm receiver. If an alarm occurs
during a remote connect, the alarm report is immediately sent to this receiver only.
When NO is selected, remote commands and programming are not accepted from the
alarm SCS-1R Receiver.
7.8
SVC RCVR NO YES
Service Receiver Authorization
YES enables remote commands and programming to be accepted from a secondary
service receiver other than the alarm SCS-1R Receiver. The Remote Key option can also
be required.
With YES selected, the panel requests the service receiver key the first time it is
contacted by the service receiver. The panel retains this service receiver key in memory
and accepts remote commands from the service receiver.
If an alarm occurs during a remote connect, the panel disconnects from the service
receiver and calls the alarm receiver. Alarm reports are only sent to the alarm receiver.
It is important that the alarm receiver key and the service receiver key programmed at
the central station are NOT the same so the panel can determine the difference between
receivers.
When NO is selected remote commands and programming are not accepted from a
secondary service receiver.
This option must be YES to allow programming from a directly connected computer or an
iCOM/iCOM-E.
7.9
Manufacturer Authorization
Select YES to allow DMP Technical Support technicians to access the panel during
system service or troubleshooting. This authorization automatically expires within
one hour.
DMP remote service is provided on a read only basis: DMP technicians can look
at the system programming and make suggestions only. Alterations can only be
accomplished by installing company service personnel.
7.10
Allow Network Remote
This option displays only if the panel has network capability. YES allows remote
programming over the network. Changing this prompt does not change any other
network programming prompts. Default is YES.
7.10.1
NETWORK PROG
Network Programming Port
PORT:
2001
Enter the programming port number. The programming port identifies the port used
to communicate messages from the panel. The default Programming Port setting is
2001.
7.10.2
Encrypt Network Remote
YES encrypts data sent over network. Default is NO.
7.11
Allow Cellular Remote
YES allows remote programming using cellular connection. Default is YES.
7.11.1
First GPRS APN
Enter the first APN (Access Point Name). This allows an access point for cellular
communication and is used to connect to a DNS network. The APN may contain two
lines of 16 characters to equal 32 characters. Default is set to NMRX.CA.APN.
Second GPRS APN
Enter the second APN (Access Point Name). This works as a backup in case the first
APN fails. The APN may contain two lines of 16 characters to equal 32 character
Default is set to INTERNET.COM.
PC MODEM NO YES
MANUFACTURER
AUTH?
NO YES
ALLOW NETWORK
REMOTE? NO
YES
NMRX.CA.APN
-
FIRST GPRS APN:
INTERNET.COM
-
SECOND GPRS APN:
ENCRYPT NETWORK
REMOTE?
NO YES
ALLOW CELL
REMOTE? NO
YES