XR500 Series Canadian Programming Guide
32
SYSTEM OPTIONS
9.27
PANIC SUPERVISION:
NO YES
Panic Supervision
Select YES to enable a 30 day supervision of the Model 1145-1-B-PSV key fob.
Default is NO.
This option allows a key fob that is lost or has a dead battery to be identified at the
Central Station host automation system as a missing transmitter, without the need to
apply a supervision time in zone information programming. SCS-VR Version 1.3.6 or higher
is required to receive 1145-1-B-PSV supervision messages through the XR500 panel.
The 1145-1-B-PSV key fob supervision message is communicated to SCS-VR using all
XR500 communication paths where Panic Test is YES within Advanced Communication
programming. A supervision message is automatically sent from the key fob to SVS-VR
every four hours, resetting the 30 day countdown timer for that key fob serial number.
If the 30 day timer expires for a key fob serial number, SCS-VR will generate a zone
missing message to the host automation system. For the application where the key fob is
programmed into several XR500 Version 210 or higher panels, a supervision message sent
through any XR500 into which the key fob is programmed will satisfy the 30 day timer.
The SCS-VR zone missing message to host automation will be for the last panel account
number where the key fob successfully communicated a supervision message to SCS-VR.
The key fob MISSING is not displayed or recorded at the XR500 control panel.
In addition, this option allows for manual testing of 1145-1-B-PSV key fobs during Walk
Test (8144) or Panic Test from the user menu. A key fob that is successfully activated
during these test modes will cause an increment to the keypad display TRIPS counter and
a Verify message is sent to SCS-VR for that zone. For those 1145-1-B-PSV key fobs that
are programmed into the panel but not manually tested, a Fail message is NOT displayed
at the keypad and is not sent to SCS-VR.