Encrypted communications (xr500n/xr500e only), Programmer operation, Programmer lockout codes – DMP Electronics DMP Command Processor Panel XR500 User Manual
Page 11: Reset timeout
Digital Monitoring Products
XR500 Series Canadian Programming Guide
2
INTRODUCTION
1.3
Encrypted Communications (XR500N/XR500E only)
Some installations require secure data communications. DMP offers NIST approved AES encrypted
communication. Use a unique passphrase to enable encrypted communications and provide a secure
means for data communications. See Network Options.
An XR500E panel communicates using AES encryption. If you currently have an XR500N panel installed, you
may purchase a separate feature key to activate encrypted communications using the Feature Upgrade
process. Encrypted communication cannot be enabled on a standard XR500 panel. For more information
on the Feature Upgrade process see Section 21 in this document.
1.4
Programmer Operation
There are 21 programming sections to choose from:
Programming Item
Section in This Manual
Programming Item
Section in This Manual
Initialization
2
Output Information
12
Communication
3
Output Groups
13
Network Options
4
Menu Display
14
Messaging Setup
5
Status List
15
Device Setup
6
Printer Reports
16
Remote Options
7
PC Log Reports
17
System Reports
8
Area Information
18
System Options
9
Zone Information
19
Bell Options
10
Stop
20
Output Options
11
Set Lockout Code
21
Feature Upgrade
22
To choose a section for programming, press any top row Select key when the keypad displays the name of
that section. Sections 2 through 22 contain detailed instructions for each programming step.
1.5
Programmer Lockout Codes
The panel allows you to enter the programming function without entering a lockout code using steps
1 to 4 listed in Getting Started. We recommend, however, that you install a Lockout Code to restrict
programming to only those persons your company authorizes. You can do this by using the SET LOCKOUT
CODE feature in the Programmer. The Lockout Code restricts any unauthorized panel programming.
After resetting the panel and entering the code 6653, the keypad displays PROGRAMMER. Press COMMAND
to advance through the programming sections until SET LOCKOUT CODE displays (after STOP). Press any
top row Select key. The keypad displays ENTER CODE: – . Enter a 3 to 5 digit Programmer Lockout Code
and press COMMAND. The keypad displays ENTER AGAIN followed by ENTER CODE: –. Enter the same 3 to
5 digit code a second time and press COMMAND. The keypad displays CODE CHANGED.
Note: The panel does not accept a 5-digit Lockout Code higher than 65535.
Before accessing programmer functions enter the new code number. Write the Lockout Code number down
and keep it in a secure place with access limited to authorized persons only. Lost Lockout Codes require
the panel to be sent back to DMP for repair. You may cancel a Lockout Code by entering 00000 at the Set
Lockout Code command.
1.6
Reset Timeout
The panel has a feature that requires you to enter the Programmer within 30 minutes of resetting the
panel. After 30 minutes, if you attempt to program by entering the 6653 (PROG) code, the keypad
displays: RESET PANEL. You must reset the panel and enter the program code then begin programming
within the next 30 minutes.
If you are already in the Programmer and do not press any keys on the programming keypad for 30
minutes, the panel terminates programming. All data entered up to that time is Not saved unless you run
the Stop routine.
Note: Use the Stop routine to exit panel Programming. Ensure the keypad displays “SAVING PROGRAM” to
save all programming changes entered.
1.7
Power Up
When the XR500 Series Canadian panel is powered up after an AC power failure, any zone transitions are
not recognized for 60 seconds. Normal zone processing resumes at the end of the 60 seconds.