XR500 Series Canadian Programming Guide
Digital Monitoring Products
31
SYSTEM OPTIONS
9.22
ENHANCED ZONE
TEST: NO YES
Enhanced Zone Test
Select YES to allow enhanced zone test operation. The default is NO.
Enhanced operation allows:
• Panic Test and Walk Test functions can be restricted to operate only during an
Area 32, Shift 4 schedule if programmed. If no schedule is entered, the walk
test always operates.
• A Verify message is sent each time a zone is tested. If a zone is tripped
multiple times, a Verify message is sent for each trip. This allows the Central
Station to record the number of devices per zone.
• The Verify message for each zone test is sent at the time the trip occurs
instead of at the end of Walk Test.
• The System Test Begin and System Test End Central Station messages indicate
the type of zone being tested. The System Test Begin message also includes
the user name and number.
9.23
Dual EOL
Select YES to enable the use of dual 1K EOL resistors on panel zones one to eight.
This zone operation is used for medium or high risk ULC Listed applications. Select
NO to disable this feature. Default is YES.
Note: If using a 714, 714-8, or 714-16 for dual zone protection, program two zones
as the same name or equivalent and connect to the contact in the protected area.
Refer to the Dual Zone Protection diagram in the XR500 Series Canadian Installation
Guide for complete details.
9.24
SEND 16 CHAR
NAMES: NO YES
Send 16 Character Names
This option allows central stations to select being sent either the first 16 characters
of the name field or the entire programmed name, up to 32 characters, for user
name, user profile, zone name, area name, output name, and group name.
Select YES to have the first 16 characters of the name field sent to the central
station. Select NO to send the exact number of characters entered in the name field
from 1 up to the maximum of 32 characters. Default is YES.
Note: Using 32 character names increases the length of the DMP Serial 3 message
from the panel to the receiver. The SCS-1R receiver does not require an update to
pass these messages to the Host Automation System of the Central Station. Before
using names longer than 16 characters, determine whether the Host Automation
System of your Central Station can accept 17 to 32 character names. If not, only use
16 character names.
9.25
KEYPAD ARMED LED
ALL
Keypad Armed LED
This option displays only when using an Area system. Press any top row key to select
the operation of the Armed LED on the keypad. Select ALL to require all keypad
display areas to be armed before the keypad Armed LED turns on. Select ANY to turn
on the keypad Armed LED when any keypad display area is armed. Default is ALL.
9.26
USE FALSE ALARM
QUESTION NO YES
Use False Alarm Question
Select YES to display IS THIS A FALSE ALARM? NO YES at the keypad in place of
CANCEL VERIFY when a burglar alarm occurs. This operates for ALL/PERIM and
HOME/SLEEP/AWAY arming systems. Default is NO.
9.26
ALLOW OWN USER
CODE CHG? NO YES
Allow Own User Code Change
This option allows users without user code authority to change their own user code.
When YES is selected, the User Code menu displays USER CODE: ***** at the keypad to
allow that user to change their own code. If NO is selected, the user cannot change their
personal user code. Default is NO.
KEYPAD ARMED LED
ALL ANY
DUAL EOL NO YES