XR500 Series Canadian Programming Guide

Digital Monitoring Products

41

STATUS LIST

15.5

BURGLARY ZONES:

Burglary Zones

Specifies the keypad addresses (1 through 16) where all burglary zone alarms and

troubles display. Bur glary zones in clude Night, Day, and Exit type zones. Burglary

zone troubles remain in the list until the zone restores. All keypads are selected by

default.
For zone alarms, only the last burglary zone tripped re mains in the list. The alarm

re mains in the list un til another burglary zone goes into alarm, any area of the

system is dis armed, or 10 minutes elapse without an alarm. This ensures that if a

bur glary is in progress the last zone tripped remains in the list even if the zone is

restored.
The keypad buzzer sounds for one second on bur glary alarms.
When using LCD Keypads, the panel provides distinct speaker tones from the keypad

for Burglary:
On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off - Alarm Silence.
You can further define which keypad address shows a Burglary Zone event by

entering that area number in the Display Areas menu during Device Setup.

15.6

SPRVISORY ZONES:

Supervisory Zones

Specifies the keypad addresses (1 through 16) where all su pervisory zone alarms

and troubles display. Supervisory zones are entered in the sta tus list and sound the

keypad buzzer until a valid user code is entered at any keypad address. If a trouble

condition remains in the display, the buzzer sounds at 10:00 am daily until the

supervisory trouble is cleared from the Status List.

15.7

PANIC ZONES:

Panic Zones

Specifies the keypad addresses (1 through 16) where all panic zone alarms and

troubles display. The name of the zone remains in the list until the zone re stores.

The keypad buzzer does not sound for panic alarms or troubles.

15.8

EMERGENCY ZONES:

Emergency Zones

Specifies the keypad addresses (1 through 16) where all emer gency zone alarms and

troubles display. The name of the zone remains in the list until the zone re stores.

The keypad buzzer does not sound for emer gency alarms or troubles.

15.9

AUX 1 ZONES:

Auxiliary 1 Zones

Specifies the keypad addresses (1 through 16) where all Aux iliary 1 zone alarms and

troubles display. The name of the zone remains in the list until the zone restores.

The keypad buzzer does not sound for Auxiliary 1 alarms or troubles.
You can further define which keypad address shows an Auxiliary 1 Zone event by

entering that area number in the Display Areas menu during Device Setup.

15.10

AUX 2 ZONES:

Auxiliary 2 Zones

Specifies the keypad addresses (1 through 16) where all Aux iliary 2 zone alarms and

troubles display. The name of the zone remains in the list until the zone restores.

The keypad buzzer does not sound for Auxiliary 2 alarms or troubles.
You can further define which keypad address shows an Auxiliary 2 Zone event by

entering that area number in the Display Areas menu during Device Setup.

15.11

COMM PATH TRBL:

ALL NO YES

Communication Trouble

Specifies when communication troubles are displayed on keypads that are

programmed to display System Monitor Troubles. Default is NO.
Select YES to display communication trouble when any communication path fails.
Select ALL to display communication trouble only when all paths have failed.