DEVICE SETUP

If you do not enter any area numbers, all users with Door Access authority receives a

door access without regard to schedules. If the user code is programmed for Anti-Pass

YES, then the user is logged into all matching areas. This user is not allowed to access

these areas again until they have egressed the area. See Egress Areas.
When all areas accessed by a door are armed, the door is locked by the panel.
Note: For an All/Perimeter, Home/Sleep/Away, or Home/Sleep/Away with Guest

system, Access Areas should be left at factory default settings.

6.7

Egress Areas

Press the COMMAND key to program Egress Areas. To select an area, enter the area

number using the digit keys on the keypad. When an area is selected, an asterisk

appears next to the area number. Enter the number again to deselect the area.

Press COMMAND to display the next set of areas. Refer to the Multiple Displays

section at the beginning of this document.
Note: For an All/Perimeter, Home/Sleep/Away, or Home/Sleep/Away with Guest

system, Egress Areas should be left at factory default settings.
Note:
If an area is programmed as an access area, it cannot be programmed as an

egress area and therefore does not display during Egress Areas programming.
Use this option to detect Anti-passback violations. Anti-passback requires a user to

properly exit (egress) an area they have previously accessed. If users fail to exit

through the proper card reader location they are not granted access on their next

attempt. Users must have matching access area numbers assigned to their profile,

to receive a door access at this device. If the user is programmed for Anti-Pass

YES, then the user is logged out of all matching areas. This allows the user to again

access the area. See

Access Areas section.

If you do not enter any area numbers, all users with Door Access authority receives a

door access without regard to schedules. If you are not using the Anti-Pass feature

leave

Egress Areas blank.

6.8

DISPLAY AREAS:

Display Areas

*1 *2 *3 *4

*5 *6 *7 *8

*9 *10 *11 *12

*13 *14 *15 *16

*17 *18 *19 *20

*21 *22 *23 *24

*25 *26 *27 *28

*29 *30 *31 *32

Press the COMMAND key to program Display Areas. To select an area between 1 and

32, enter the area number using the keypad digit keys. When an area is selected, an

asterisk appears next to the area number. Enter the number again to deselect the

area. Press COMMAND to display the next set of areas. Default is all area numbers.

Refer to the Multiple Displays section at the beginning of this document.
Display Areas allows the XR500 Series burglary activities to be segmented so that

only specific area(s) and their associated operation appear at a particular keypad.

Area number(s) selected in this field affect the way users interact with the system

from this particular device. For example: Program Device 1 to show only the zone

activities and armed status of Area 1.
Enter the area number(s) that this keypad is to display. This allows specific area control

from specific keypads, as well as annunciation of zones assigned to those area(s). When

Display Areas is left defaulted (all areas selected), Menu Display and Status List items

determine whether zone alarms and troubles display at this device, regardless of area

assignment. Also, all system areas may be armed and disarmed from this device.
Note: For an All/Perimeter or Home/Sleep/Away system, Display Areas should be

left at factory default settings.
For Home/Sleep/Away with Guest arming systems, the Display Areas selection

determines which system the keypad arms and disarms. With areas 1, 2 or 3 being

the first areas selected, the keypad is assigned to the Main system. With area 4, 5 or 6

being the first areas selected, the keypad is assigned to the Guest 1 system. With area

7, 8 or 9 being the first areas selected, the keypad is assigned to the Guest 2 system.

Keypads can have additional areas assigned for Event Display.
User Action Allowed

When an area(s) is selected, the following user actions are allowed:

• Arming or Disarming of the area(s) selected from the ARM or DISARM menu

• Alarm Silence for the area(s) selected

• Zone Bypass of zones assigned to the area(s) selected

• Zone Monitor of zone assigned to the area(s) selected

• Shift schedule changes allowed for the area(s) selected

• Closing Check Schedule Extend is allowed for the area(s) selected

EGRESS AREAS: