beautypg.com

Appendix – DMP Electronics DMP Command Processor Panel XR500 User Manual

Page 72

background image

XR500 Series Canadian Programming Guide

Digital Monitoring Products

63

APPENDIX

Appendix

23.1 False Alarm Reduction

System Recently Armed report
The System Recently Armed report (S78) is sent to the receiver when a burglary zone goes into alarm

within two minutes of the system being armed.

23.2 Diagnostics function

The XR500 Series Canadian panel contains a Diagnostics function that allows you to test the communication

integrity of the LX-Bus™, identify individual zones, and also display the present electrical state of any

zone. The Diagnostics function also allows you to test the integrity of the cellular communication, cellular

signal, and email communication. To use Diagnostics, reset the panel, enter the Diagnostics code 2313

(DIAG), and press COMMAND.

Test LX-Bus
The first Diagnostic function you displayed is:

TEST LX-BUS. This function allows you to test the ability of

the 481, 462N, 462P, 463C, 463G and 472 Interface Cards to communicate with zone and output expander

modules connected to their LX-Bus circuits.

To continue, press any top row Select key. The keypad displays

LX-BUS:. Using the digit keys, enter the

LX-Bus number, 1 to 5, to test that LX-Bus circuit. The keypad now displays

ADDRESS: - . Enter a 2-digit

LX-Bus device address and press COMMAND. When testing LX-Bus devices, enter only the addresses to

which the modules have been set.

Important Note: A device address is not the same as a zone number. If you are testing 714 or 715 Zone

Expander Modules, which each contain four zones, the device address is the first zone number. When the

panel polls a 714 on the LX-Bus, it recognizes it as a four zone device and does not poll the remaining

three zones. The 714 module internally polls the remaining zones and transmits any status changes to the

panel. This greatly reduces the amount of time it takes the panel to poll all LX-Bus devices.

The keypad next displays

TESTING . . . STOP during the device testing. At any time, you can Select

STOP to end polling. The panel records the number of no responses from the device. If all polls are

received back by the panel correctly, the keypad displays

00000/65535 FAIL.

If one or more polling attempts fail, the keypad displays

* * * * */65535 FAIL with the * representing the

number of failed polling attempts. A display of

65535/65535 FAIL indicates a problem with the interface

card or its LX-Bus wiring such as a bad or broken wire, harness not properly connected, or excessive noise

or distance. It can also mean that a zone number was entered that did not match a device address. Press

the Back Arrow key to enter a new device address or press COMMAND to exit the

TEST LX-BUS.

Zone Finder
The second Diagnostic function is the Zone Finder. Press COMMAND to display

ZONE FINDER. This function

allows you to identify individual zones on devices connected to the LX-Bus of an interface card, the panel,

or any zones on the keypad data bus. To use

ZONE FINDER, press any top row Select key. The display

changes to

FAULT ZONE. The next zone on the system that changes from a normal to an open or shorted

state is displayed as

ZONE NO: * * *. To continue, press the Back Arrow key.

Zone State
Press the COMMAND to display the third Diagnostic function:

ZONE STATE. This function allows you to

enter any zone number and check its current electrical state (Normal, Open, or Shorted). Press any Select

key. The display changes to

ZONE NUMBER: _ . Enter in the zone number you want to check and press

COMMAND. The panel displays the current state of the zone as

NRML (normal), OPEN, or SHORT.

LX-Bus Status
The fourth Diagnostic function is the

LX-BUS STATUS. This function allows the panel to poll all devices

connected to the LX-Bus of an interface card and check for any Overlapped, Missing, or Extra addresses.

Below is a description of each status item:

Overlap - An overlap occurs when one device address is the same as any of the last three zones on another

714 or 715. The overlap feature cannot determine when two devices have the same address.

Example: Model 714 Address 00 = Zones 500 501 502 503, and the Model 711 Address 02 = Zone 502.

Zone 502 would report as an Overlap because both the 714 and 711 have devices set to 502.

Missing - A missing occurs when a zone between 500 and 999 has been programmed in ZONE INFORMATION

and no device with that zone address has been installed on the LX-Bus. To correct the problem, check

your zone programming and zone expansion module addressing.

Extra - A device is installed on the LX-Bus but none of its zones are programmed into the system.

MAC Address
Short for Media Access Control address. This hardware address uniquely identifies each network node. Not

to be confused with an IP address, which is assignable. In the Diagnostics function, the MAC address is the

panel on-board network hardware address. Press any top row Select key to display the panel MAC address.

Press the COMMAND key to view the next prompt.