beautypg.com

Fa series wireless, 12  wireless, 1  check-in time – DMP Electronics DMP Command Processor Panel XR500 User Manual

Page 65: 2  internal contact, 3  end-of-line, 4  normally open, 5  next zone, 13  alarm action, 14  disarmed open, 12 wireless

background image

Digital Monitoring Products

XR500 Series Canadian Programming Guide

56

ZONE INFORMATION

ARM AREAS: PERIM

In an All/Perimeter or Home/Sleep/Away system, this specifies the area to be

armed by the Key Fob button being programmed. For All/Perimeter systems,

choose PERIM or ALL, for Home/Sleep/Away or Home/Away systems, choose

HOME, SLEEP, or AWAY.
Note: Areas 3 and higher in an All/Perimeter system, and areas 4 and higher in a

Home/Sleep/Away system are not available for use.
After selecting the areas, for one-button key fobs the Zone No.: prompt

displays. For two-button or four-button key fobs, the Key Fob Button Selection

option displays to program additional buttons.

19.11.10

OUTPUT NO: XXX

Output Number

You can specify a relay output to operate when OUT (Output), PN (Panic), PN2

(Panic 2), EM (Emergency), or EM2 (Emergency 2) is selected for a key fob

Button Action and the button is pressed. Valid range is 1 to 6, 500 to 999,

D1 to D16, or G1 to G20. For an output turned on by a PN, PN2, EM, or EM2

button action, the output turns off when any area is disarmed.
To enter an output number, press a top row Select key followed by the output

number. Press the COMMAND key.

19.11.11

OUTPUT ACTION:

yyy: XXXXXXXX

Output Action

This option allows you to define the output action (STD, PLS, MOM, TGL, OFF)

for the selected output number. The default is Steady.
yyy = the name of the button being programmed (TOP, BTM, LFT, RGT).

xxxxxxxx = the currently defined output action.

OUTPUT ACTION?

STD PLS MOM TGL

STD (Steady) - The output is turned on and remains on.
PLS (Pulse) - The output alternates one second on and one second off.

The pulsing rate for a Model 716 relay attached to the LX-Bus is 1.6 seconds.
Note: Pulse is not available for key fob button output programmed D1 to D16 or

G1 to G20.
MOM (Momentary) - The output is turned on only once for one second.
TGL (Toggle) - The output alternates between the on state and off state. Each

button press toggles the output state.
Note: Toggle is not available for key fob button output programmed G1 to G20.

OUTPUT ACTION?

OFF

OFF (Off) - The output is turned off. If programmed, the output was turned

on by some other means such as another button press, a zone action, or a

schedule.
Note: When the output is assigned to PN/PN2 or EM/EM2 button action and is

turned on, the output turns off when any area is disarmed.
When the output action is steady, pulse or toggle and the output is turned on,

the output remains on until:

— the output cutoff time expires

— the output is reset from the keypad menu

— toggled off

19.11.12

NEXT ZONE NO YES

Next Zone

Select YES to return to the ZONE NO: - prompt to program a new zone. Select

NO to display the Alarm Action option.

Note: All wireless programming is stored in the XR500 Series Canadian panel. The 1100X Wireless

Receiver obtains the necessary programming information from the panel each time the receiver powers up,

when the programmer STOP routine is selected or the panel is reset. The receiver memory refresh takes

up to 10 seconds to complete depending on the number of wireless zones programmed and the Red LED

remains on during this time. Normal receiver operation is inhibited during the memory refresh period.