15  report to transmit, 16  output number, 17  output action – DMP Electronics DMP Command Processor Panel XR500 User Manual
Page 66: Report to transmit, Output number, Output action
XR500 Series Canadian Programming Guide
Digital Monitoring Products
57
ZONE INFORMATION
FA Series Wireless
For an FA Series Remote Wireless Receiver set the House Code to 99. See House Code programming in
System Options. Only zones 500 to 699 can be programmed as FA Series Wireless zones for maximum of
200 Wireless Zones.
For a DMP 1100X Wireless Receiver see section 16.10.
19.12
ZONE INFORMATION
WIRELESS? NO YES
Wireless
Select YES to program a wireless zone connected to an FA Series FA400-DMP Remote
Wireless Receiver. Press the COMMAND key to continue with wireless programming.
19.12.1
CHECK IN TM:
60
Check-in Time
You can set wireless transmitters to check in automatically every 10, 30, or 60
seconds or not at all. To change the 60 second default, press any top row Select
key to display NONE 10 30 60. Select the check-in time you want for this zone.
Note: Refer to the Wireless Check-in and Supervision Time Definitions section
of the Appendix for supervision information.
19.12.2
INT CONT NO YES
Internal Contact
Select YES to use an internal contact on the wireless transmitter. Select NO
to use an external contact. When you select NO, the following two prompts
display.
19.12.3
EOL NO YES
End-of-Line
Select YES to supervise an external contact connected to the wireless
transmitter. At the contact, install a 2.2k Ohm End-of-Line resistor in parallel
for Normally Open contacts and in series for Normally Closed contacts.
19.12.4
NRM OPEN NO YES
Normally Open
Select NO if the contact connected to the wireless transmitter is Normally
Closed.
19.12.5
NEXT ZONE NO YES
Next Zone
Select YES to return to the ZONE NO: - prompt to program a new zone. Select
NO to display the Alarm Action option.
19.13
ALARM ACTION . . . .
Alarm Action
This option allows you to change any Zone Type standard definitions. When the Zone
Type is specified, the Alarm Action for that zone is stored in memory.
If the Zone Type is Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 it is a
non-24-hour zone and the Alarm Action programing begins with Disarmed Open.
If the Zone Type is Fire, Panic, Emergency, or Supervisory it is a 24-hour zone that is
always armed and the Alarm Action programming begins with Armed Open.
The Fire Verify Zone Type functions the same as Fire Type, with the following
exceptions: When a Fire Verify zone initiates an alarm, the panel performs a Sensor
Reset. If any Fire Verify zone initiates an alarm within 120 seconds after the
reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the cycle is
repeated and a zone fault report is sent to the receiver.
Do NOT program Fire Verify Zone Types for Zone Retard.
19.14
DISARMED OPEN
Disarmed Open
Defines the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to define: Report to transmit, Relay Output to
activate, and Relay Output action.
You must also make these selections for the Disarmed Short, Armed Open, and Armed
Short zone conditions. Press COMMAND to continue.