6  panic alarm output, 7  ambush output, 8  entry output – DMP Electronics DMP Command Processor Panel XR500 User Manual
Page 43: 9  exit output, 10  ready output, 11  telephone trouble output, 12  late to close output, 13  device fail output, 14  sensor reset output, Panic alarm output
Digital Monitoring Products
XR500 Series Canadian Programming Guide
34
OUTPUT OPTIONS
Output Options
11.1
OUTPUT OPTIONS
Output Options
This section allows you to program panel output options. The panel provides two
Form C relays (1 and 2) and four switched ground (open collector) outputs numbered
3 to 6. Expand the system up to 500 additional relay outputs using J22 LX-Bus on
the panel, multiple 716 Output Expander Modules, and up to five interface cards. In
addition, 45 wireless outputs are available when using the 1100X wireless receiver.
Refer to the XR500 Series Canadian Installation Guide (LT-0681) for complete
information.
Select from the following output numbers:
• 1 to 6
• 450 to 474 — Slow response time
* wireless outputs (activates within 15 seconds)
• 480 to 499 — Fast response time
* wireless outputs (activates within 1 second)
• 500 to 999 — LX-Bus output, Relay output, Zone expansion output
• D1 to D16 — Keypad door strike relay for addresses 1-16
• G1 to G20 — Output group
* The response time of a wireless output is the time it takes for a wireless output to
activate once the panel event occurs. You determine whether a wireless output is a
slow or fast response based on the output number assigned. A slow response output
number extends battery life, but response time may be up to 15 seconds. A fast
response output number responds within 1 second, but reduces battery life. Refer
to the specific wireless output installation guide to determine battery life.
11.2.1
CO OUTS: - - - - - -
Cutoff Output
Outputs 1 to 6 can be entered here to turn off after a time specified in CUTOFF
TIME. To disable this option, press any Select key to clear the display then press
COMMAND. The Cutoff Output displays dashes when no outputs are selected.
11.2.2
CUTOFF TIME: 0
Output Cutoff Time
If a Cutoff Output (1-6) is assigned, enter a Cutoff Time of 1 to 99 minutes for the
output to remain on. Enter 0 (zero) for continuous output.
11.3
COMM TRBL OUT: 0
Communication Trouble Output
Enter the output number to turn on when a DD system fails to communicate on
three successive dial attempts or if the backup communication line transmits a
report. The Communication Trouble Output also turns on when NET is selected
as the primary communication method and NET communication fails after one
minute. When NET communication is restored the Communication Trouble Output
automatically turns off.
To manually turn the output off, disarm any area or select Off for the output number
in the User Menu Outputs On/Off section. Enter 0 (zero) to disable this output.
11.4
FIRE ALR OUT: 0
Fire Alarm Output
Enter the output number to turn on when a fire type zone is placed in alarm. The
output is turned off using the Sensor Reset option while no additional fire type zones
are in alarm. Enter 0 (zero) to disable. This output is not compatible with Cutoff
Outputs.
11.5
FIRE TRB OUT: 0
Fire Trouble Output
Enter the output number to turn on when a fire type zone is placed in trouble,
when a supervisory type zone is placed in trouble, or when any system monitor (AC,
Battery, Phone Line 1 or Phone Line 2) is placed in trouble. The output turns off
when all fire and supervisory type zones, or system monitors are restored to normal.
Enter 0 (zero) to disable this output. This output is not compatible with Cutoff
Outputs. This output can be connected to a lamp, LED, or buzzer using the DMP
Model 716 Output Expansion Module.