OUTPUT OPTIONS
11.15
CLS WAIT OUT: 0
Closing Wait Output
Enter the output number to turn on for approximately four (4) seconds when Closing
Wait is programmed as YES and the panel successfully communicates the closing
message at arming. If the closing message does not communicate successfully, this
output does not turn on.
11.16
ARM-ALARM OUT: 0
Arm-Alarm Output
Enter the output number to turn on steady when any area of the system is armed. If
an alarm occurs causing the keypads to turn Red, this output pulses and continues to
pulse for approximately five (5) minutes after the panel is disarmed. Enter 0 (zero)
to disable.
Wireless Outputs
• The Arm-Alarm Output is compatible with the Model 1117 Wireless LED
Annunciator and the Model 1116 Wireless Relay Output connected to a Model
572 Indicator LED.
• When the Model 1117 is battery operated, the LED is off when the system is
armed to conserve battery life. If an alarm occurs, the output flashes quickly.
• When using the Model 1116 connected to a Model 572, the LED is on when the
system is armed. If an alarm occurs, the output pulses.
• To operate the Arm-Alarm output within one second, program a fast response
number from 480 to 499. Fast response operation reduces overall wireless
output battery life.
• To operate the Arm-Alarm output within 15 seconds, program a slow response
number from 450 to 474. Slow response operation increases overall wireless
output battery life.
11.17
SUPV ALM OUT: 0
Supervisory Alarm Output
Enter the output number to turn on when a supervisory zone type is placed into an
alarm. The output turns off when all supervisory type zones are restored to normal.
Enter 0 (zero) to disable. Default is 0.