XR500 Series Canadian Programming Guide
Digital Monitoring Products
53
ZONE INFORMATION
consecutive zone numbers. Default is Contact 1.
For example, use serial number 08345678 to program Contact 1 for Zone 561,
Contact 2 for Zone 562, Contact 3 for zone 563, and Contact 4 for zone 564.
A tamper on the 1114 is transmitted as the zone number assigned to Contact 1.
ALREADY IN USE
ZONE NUMBER: XXX
This message displays when the Contact is already programmed for another
zone. The programmed zone number displays.
ZONE INFORMATION
NORM OPN NO YES
This option only displays when EXT is selected as the Contact type. For external
devices connected to the 1101 or 1103 terminal block, select NO to use normally
closed (N/C) contacts. Select YES to use normally open (N/O) contacts. Default
is NO.
19.10.3
TRANSMITTER
SUPRVSN TIME: 240
Supervision Time
Press any top row key to select the supervision time required for the wireless
zone. Press COMMAND to accept the default time. Default is 240 minutes.
Note: Refer to the Wireless Check-in and Supervision Time Definitions section
of the Appendix for supervision information.
SELECT MINUTES:
0 3 60 240
Press the Select key under the required number of minutes. The transmitter
must check in at least once during this time or a missing condition is indicated
for that zone. 1100 Series transmitters automatically checkin based on the
supervision time selected for the wireless zone, no additional programming
is needed. If two zones share the same transmitter, the last programmed
supervision time is stored as the supervision time for both zones. Zero (0)
indicates an unsupervised transmitter.
The 3 minute supervision time is only available for zone types of Fire (FI), Fire
Verify (FV), and Supervisory (SV).
Note: When the panel is reset or a receiver is installed or powered down and
powered up, the supervision timer restarts for all wireless zones.
19.10.4
LED OPERATION
NO YES
LED Operation
Select YES to turn on an 1142 Hold-up transmitter LED during Panic or
Emergency operation. Select NO to turn the LED off during Panic or Emergency
operation. The LED always operates when the transmitter case is open and the
tamper is faulted. Default is YES.
19.10.5
DISARM DISABLE
NO YES
Disarm/Disable
Select YES to disable the zone tripped message (short) to the 1100X Series
Receiver from the 1126 PIR transmitter during the disarmed period. When
disabled, the 1126 only sends supervision, tamper and low battery messages
during the disarmed period to extend transmitter battery life. Select NO to
always send zone tripped messages in addition to supervision, tamper and low
battery. Default is YES.
19.10.6
WIRELESS PIR
PULSE COUNT: 4
PIR Pulse Count
Select the number of infrared pulses (2 or 4) the 1126 PIR should sense before
sending a short message to the 1100X Series Receiver. Default is 4.
19.10.7
WIRELESS PIR
SENSITIVITY:LOW
PIR Sensitivity
Select the sensitivity setting for the 1126 PIR. Selecting LOW sets the 1126 to
operate at 75% sensitivity for installations in harsh environments. Selecting
HIGH sets the PIR to maximum sensitivity. Default is LOW.
19.10.8
NEXT ZONE NO YES
Next Zone
Select YES to return to the ZONE NO: - prompt to program a new zone. Select
NO to display the Alarm Action option.