XR500 Series Canadian Programming Guide

Digital Monitoring Products

53

ZONE INFORMATION

consecutive zone numbers. Default is Contact 1.
For example, use serial number 08345678 to program Contact 1 for Zone 561,

Contact 2 for Zone 562, Contact 3 for zone 563, and Contact 4 for zone 564.
A tamper on the 1114 is transmitted as the zone number assigned to Contact 1.

ALREADY IN USE

ZONE NUMBER: XXX

This message displays when the Contact is already programmed for another

zone. The programmed zone number displays.

ZONE INFORMATION

NORM OPN NO YES

This option only displays when EXT is selected as the Contact type. For external

devices connected to the 1101 or 1103 terminal block, select NO to use normally

closed (N/C) contacts. Select YES to use normally open (N/O) contacts. Default

is NO.

19.10.3

TRANSMITTER

SUPRVSN TIME: 240

Supervision Time

Press any top row key to select the supervision time required for the wireless

zone. Press COMMAND to accept the default time. Default is 240 minutes.
Note: Refer to the Wireless Check-in and Supervision Time Definitions section

of the Appendix for supervision information.

SELECT MINUTES:

0 3 60 240

Press the Select key under the required number of minutes. The transmitter

must check in at least once during this time or a missing condition is indicated

for that zone. 1100 Series transmitters automatically checkin based on the

supervision time selected for the wireless zone, no additional programming

is needed. If two zones share the same transmitter, the last programmed

supervision time is stored as the supervision time for both zones. Zero (0)

indicates an unsupervised transmitter.

The 3 minute supervision time is only available for zone types of Fire (FI), Fire

Verify (FV), and Supervisory (SV).
Note: When the panel is reset or a receiver is installed or powered down and

powered up, the supervision timer restarts for all wireless zones.

19.10.4

LED OPERATION

NO YES

LED Operation

Select YES to turn on an 1142 Hold-up transmitter LED during Panic or

Emergency operation. Select NO to turn the LED off during Panic or Emergency

operation. The LED always operates when the transmitter case is open and the

tamper is faulted. Default is YES.

19.10.5

DISARM DISABLE

NO YES

Disarm/Disable

Select YES to disable the zone tripped message (short) to the 1100X Series

Receiver from the 1126 PIR transmitter during the disarmed period. When

disabled, the 1126 only sends supervision, tamper and low battery messages

during the disarmed period to extend transmitter battery life. Select NO to

always send zone tripped messages in addition to supervision, tamper and low

battery. Default is YES.

19.10.6

WIRELESS PIR

PULSE COUNT: 4

PIR Pulse Count

Select the number of infrared pulses (2 or 4) the 1126 PIR should sense before

sending a short message to the 1100X Series Receiver. Default is 4.

19.10.7

WIRELESS PIR

SENSITIVITY:LOW

PIR Sensitivity

Select the sensitivity setting for the 1126 PIR. Selecting LOW sets the 1126 to

operate at 75% sensitivity for installations in harsh environments. Selecting

HIGH sets the PIR to maximum sensitivity. Default is LOW.

19.10.8

NEXT ZONE NO YES

Next Zone

Select YES to return to the ZONE NO: - prompt to program a new zone. Select

NO to display the Alarm Action option.