3  supervision time, 4  led operation, 5  disarm/disable – DMP Electronics DMP Command Processor Panel XR500 User Manual
Page 61: 6  pir pulse count, 7  pir sensitivity, 3 supervision time, 4 led operation, 5 disarm/disable, 6 pir pulse count, 7 pir sensitivity
Digital Monitoring Products
XR500 Series Canadian Programming Guide
52
ZONE INFORMATION
19.9
NEXT ZN? NO YES
Next Zone
Select YES to terminate zone programming. The display returns to Zone Number,
allowing you to enter a new zone number. Select NO to make alter ations to the
Alarm Action for a zone. Alarm Action is defined beginning with section 16.12.
To program zones for wireless operation, select NO at the NEXT ZONE - NO YES
option. The WIRELESS NO YES option displays. If the zone you are programming
is intended for wireless devices, select YES. Select NO to continue programming
non-wireless zones in the 500 to 999 range.
• Zones 400 to 449 can be programmed for 1100 Series Key Fobs.
• Zones 500 to 699 can be programmed for FA Series Wireless.
• Zones 500 through 999 can be programmed for DMP 1100 Series Wireless.
DMP Wireless
For a DMP 1100X Wireless Receiver set the House Code from 1 to 50. See House Code programming
in System Options. Zones 500 through 999 can be programmed as Wireless zones. Set the XR500 Series
Canadian panel J23 jumper to X to enable on-board DMP Wireless operation. Briefly reset the panel using
the J16 jumper to activate Wireless operation. Refer to the XR500 Series Canadian Installation Guide
(LT-0681).
For an 1100 Series Key Fob see section 19.11.
For an FA Series Remote Wireless Receiver see section 19.12.
NOTE: All wireless programming is stored in the XR500 Series Canadian panel. The 1100X Wireless
Receiver obtains the necessary programming information from the panel each time the receiver powers
up, when the programmer STOP routine is selected or the panel is reset. The receiver memory refresh
takes up to 10 seconds to complete depending on the number of wireless zones programmed and the Red
LED remains on during this time. Normal receiver operation is inhibited during the memory refresh period.
19.10
Wireless
Select YES to program this zone as a DMP wireless zone. You must program
the wireless House Code prior to adding DMP wireless zones to the system.
See House Code programming in System Options. Default is NO.
19.10.1
TRANSMITTER
SERIAL#: XXXXXXXX
Serial Number Entry
E
nter the eight-digit serial number found on the wireless device.
ALREADY IN USE
ZONE NUMBER: XXX
This message displays when the serial number is already programmed for
another zone. The programmed zone number displays.
19.10.2
TRANSMITTER
CONTACT:XXXXXXXX
Contact
This option displays if the serial number entered is for an 1101 or 1103 Universal
Transmitter or 1114 Wireless Four-Zone Expander. Press any top row key to
select the contact.
TRANSMTR CONTACT
INT EXT
This option displays when programming an 1101 or 1103 Transmitter. Select INT
to use the internal reed switch contacts. Select EXT to connect an external
device to the 1101 or 1103 terminal block. Default is INTERNAL.
By allowing both of the Model 1101 or 1103 transmitter contacts (INT and
EXT) to be used at the same time, two zones may be programmed from
one transmitter. When using both contacts, you must use consecutive zone
numbers. Zones 531 and 532 or zones 890 and 891 are acceptable zone
assignments.
For example, program transmitter serial number 01345678 as Zone 521 with
an INT contact type and Zone 522 with an EXT contact type. The same serial
number is used for both zones.
TRANSMTR CONTACT
1 2 3 4
This option displays when programming the 1114 Wireless Four-Zone Expander
with four input contacts. The same serial number is used for all four contacts.
Select the contact number to program. When using the contacts, you must use
ZONE INFORMATION
WIRELESS? NO YES