PC LOG REPORTS
PC Log Reports
17.1
PC LOG REPORTS
PC Log Reports
This section allows you to program the types of PC Log Reports the panel sends
through the 462N Network Interface Card or through the J21 Serial Connector directly
on the XR500 Series Canadian panel. The reports include information such as the type
of activity, time and date of the activity, and user name and number. These data
reports can be accessed from a PC using the Advanced Reporting Module. See the
Installation Guide (LT-0681CAN) for detailed J21 setup information or the User’s Guide
(LT-0683CAN) for more information.
Note: The network connection that sends PC Log Reports is not monitored for network
trouble. The PC Log Reports option should NOT replace the primary communication
method or act as a backup communication method.
If there is trouble with the network connection, the panel continues to attempt to
send the PC Log Reports until the connection is reestablished. The panel then sends
the reports. A Network Trouble message is
NOT sent if the connection is lost since this
report tool is not designed to be monitored by a receiver. The PC Log Reports have
the lowest priority of panel reports sent.
For information about the 462N card capabilities with PC Log Reports and Network
Communication method, see 462N Card Examples in the Appendix.
Note: The PC Log Address String entered CANNOT be the same as that entered in
Communication.
17.2
COMM TYPE: NONE
Communication Type
NONE NET 232
Select the Communication Type to send the PC Log Reports. Default is NONE.
17.3
NET IP ADDRESS
Net IP Address
This option displays when the Communication Type for PC Log Reports is NET. Enter
the IP address containing up to 16 characters. The Net IP Address must be unique and
cannot be duplicated on the network. Enter all 12 digits and leave out the periods.
For example, enter IP address 192.168.0.250 as 192168000250. The periods display
automatically.
17.4
NET PORT 2001
Net Port
This option displays when Communication Type for PC Log Reports is Net. Enter the
Port number. Valid numbers are from 0 to 65535. Default is 2001.
17.5
232 COMM PORT: O
232 Communication Port
This option displays when Communication Type for PC Log Reports is 232. To enable
PC Log Reports, select either the on-board connector (O) or select A, B, C, D or E for
the corresponding slot in use on the DMP Model 462N Network Interface card. The
slots are labeled from left to right, beginning with A. Default is O.
Set the XR500 Series panel J23 jumper to R and briefly reset the panel using the J16
jumper to activate RS-232 operation.
17.6
232 SETUP:
232 Setup
This option displays when Communication Type for PC Log Reports is 232. Enter up to
32 characters.
17.7
ARM/DIS
NO YES
Arm and Disarm Reports
Sends arming, disarming and Late to Close events. Includes the area number, name
and action, the user number and name, and the time and date.
17.8
ZONE NO YES
Zone Reports
Sends changes in the status of active zones. Includes the zone number, name, type,
the action (alarm, trouble, bypass, etc.), user number (if applicable), and area name.
For a Walk Test, Verify and Fail messages are sent for each zone.
17.9
USR CMDS NO YES
User Command Reports
Sends user code changes, schedule changes, and door access denied events.