15  closing wait output, 16  arm-alarm output, Closing wait output – DMP Electronics DMP Command Processor Panel XR500 User Manual
Page 44: Arm-alarm output

XR500 Series Canadian Programming Guide
Digital Monitoring Products
35
OUTPUT OPTIONS
11.6
PANIC ALM OUT: 0
Panic Alarm Output
Enter the output number to turn on when any Panic type zone is placed in an alarm
condition. The output is turned off after all Panic zones are restored from an alarm
condition and a Sensor Reset is performed. Enter 0 (zero) to disable.
Wireless Outputs
• The Panic Alarm is compatible with the Model 1118 Wireless Remote Indicator
Light and the Model 1116 Wireless Relay Output connected to a Model 572
Indicator LED.
• When a Panic Alarm occurs, the LED turns on steady for five minutes and then
turns off.
• When a Panic Test is initiated from the keypad, the LED flashes quickly for five
minutes.
• For a Panic Alarm, a fast response wireless output number is recommended.
11.7
AMBUSH OUT: 0
Ambush Output
Enter the output number to turn on when an Ambush code is entered at a keypad.
The output is turned off using the Sensor Reset option. Enter 0 (zero) to disable.
11.8
ENTRY OUT: 0
Entry Output
Enter the output number to turn on at the start of the entry delay time. The output
turns off when the area is disarmed or the entry delay time expires. Enter 0 (zero)
to disable.
11.9
EXIT OUT: 0
Exit Output
Enter the output number to turn on when an exit delay time starts in any area of
the system. The output turns off when the area arms or when the arming has been
stopped. Enter 0 (zero) to disable.
11.10
READY OUT: 0
Ready Output
Enter the output number to turn on when all disarmed burglary zones are in a
normal state. The output is turned off when any disarmed burglary type zone is in
a bad state. Enter 0 (zero) to disable. This output is not compatible with Cutoff
Outputs.
11.11
PH TRBL OUT: 0
Telephone Trouble Output
Enter the output number to turn on when the phone line monitor on the panel phone
line is lost. Enter 0 (zero) to disable this output.
11.12
LATE CLS OUT: 0
Late To Close Output
Enter the output number to turn on at the expiration of a Closing schedule. The
output activates simultaneously with the CLOSING TIME! keypad display. The output
is turned off when the area is armed, the Closing is extended, or the schedule is
changed. Enter 0 (zero) to disable this output.
11.13
DVC FAIL OUT: 0
Device Fail Output
Enter the output number to turn on when an addressed device fails to respond to
polling from the panel. A Missing Device report is sent to the receiver. The output
is turned off when the device responds to polling or is removed from programming in
the system. Enter 0 (zero) to disable this output and LX-Bus™ device fail reporting
to the receiver. If any addressed device is unsupervised, this output cannot be used.
11.14
SNSR RST OUT: 0
Sensor Reset Output
Enter the output number to turn on when a Sensor Reset is performed at a keypad.
The output turns off automatically 5 seconds later. This function can be used to
reset smoke detectors that are operated by an external power supply through a
Model 716 Output Expander Module. Enter 0 (zero) to disable this output.