Output groups, 1  output groups, 2  group number – DMP Electronics DMP Command Processor Panel XR500 User Manual
Page 46: 3  group name, 4  output number, Group number, Group name, Output number, Output information
XR500 Series Canadian Programming Guide
Digital Monitoring Products
37
OUTPUT INFORMATION
Output Information
12.1
OUTPUT INFO
Output Information
This section allows you to program wireless outputs and name wired outputs.
12.2
OUTPUT NO. X X X
Output Number
Enter an output number. Entry range is 1 to 6, 450 to 474, 480 to 499, 500 to 999.
In order for wireless output troubles to display at a keypad, the keypad address must
be specified at the Auxiliary 1 Zones prompt in the Status List programming.
12.3
OUTPUT NAME
Output Name
This section allows you to define a 32 character alphanumeric name for any output
numbers. The name can display on the keypad when a user performs the browser
feature at Outputs On/Off. See the XR100/XR500 User’s Guide (LT-0683CAN)
Appendix for browser operation.
12.4
Output Real-Time Status
Selecting YES allows Real-Time Status reports, such as Output ON, OFF, PULSE, or
TEMPORAL to be sent using PC Log reports. Selecting NO disables Real-Time Status
for this output device. Default is NO.
12.5
SERIAL#: XXXXXXXX
Serial Number
This option and the next option only display when the output number entered is for
a wireless output. Enter the eight-digit serial number found on the wireless device.
ALREADY IN USE
OUTPUT NO: XXX
This message displays when the serial number is already programmed for another
output. The programmed output number displays.
12.6
SUPRVSN TIME: 240
Supervision Time
Press any top row key to select the supervision time required for the wireless
output. Press COMMAND to accept the default time. Default is 240 minutes.
Note: Refer to the Wireless Check-in and Supervision Time Definitions section of the
Appendix for supervision information.
SELECT MINUTES:
0 3 60 240
Press the Select key under the required number of minutes. The wireless output
must check in at least once during this time or a missing condition is indicated for
that output. Zero (0) indicates an unsupervised transmitter.
The 3 minute supervision time is only available if using an 1135 Wireless Siren.
Note: When the panel is reset, a receiver is installed or powered down and powered
up, or programming is complete, the supervision timer restarts for all wireless
outputs.
12.7
Trip with Panel Bell Option
This option displays when the wireless device is an 1135 wireless siren. Select YES to
have the 1135 wireless siren follow the panel’s bell output cadence for the zone type
and bell cutoff time up to 15 minutes. Default is YES.
OUTPUT REAL-TIME
STATUS NO YES
TRIP WITH PANEL
BELL
NO YES