Section 7 programming, 1 ul 864 programming requirements, 2 modules – SilentKnight 5808 User Manual
Page 93: Ul 864 programming requirements -1, Modules -1, On. section 7 of this, S. section 7 con, Section 7 of th
151274-L8
7-1
Section 7
Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator.
Each subsection discusses these menu options in detail. All options described in this section can be performed
using the Silent Knight Software Suite 5660.
7.1
UL 864 Programming Requirements
7.2
Modules
This section lists the options available under the module option in the program menu. The following modules are
available for the control panel: 5860 remote fire alarm annunciator, 5824 serial/parallel printer interface module,
5496 intelligent power module, 5880 LED I/O module, and 5865 LED annunciator.
Important!
Before any customized programming is done, Jump-start should be run first. After Jump-start is run,
thoroughly test the system. The reason the system should be tested after Jump-start is because Jump-start
automatically programs the system, searching for and configuring all SLC and SBUS devices it finds. Jump-
start allows you to confirm the integrity of the installation prior to performing any custom programming.
After determining that the hardware is properly installed, custom programming can be performed. Refer to
Section 6.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES: This product incorporates field programmable
software. In order for the product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming
features or options must be limited to specific values or not used at all as indicated
below.
Programming Option
Menu Item
Permitted in
UL 864 (Y/N)
Possible
Settings
Settings
Permitted in
UL 864
Time Options
Low AC Report
Delay
Yes
0–30 hours
1–3
Display Oldest Event
Y (Enabled)
Yes
Yes & No
Yes
N (Disabled)
No
Yes & No
No
Alarm Verification
Alarm
Verification
Yes
1-250
1-60