Model 5808 Basic Operating Instructions

These Instructions must be framed and displayed next to the 5808 panel in
accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems.
Test the system in accordance to NFPA 72.

Operation

Task to Perform

Silence Alarms and
Troubles

Press SILENCE then rotate the key or enter a code if prompted. Silence LED will light.

Reset Alarms

Press RESET then rotate the key or enter a code if prompted.

Acknowledge Alarms
and Troubles

Press ACK then enter a code if prompted. When the Alarm or Trouble is acknowledged an
A will appear in the annunciator display as shown Below.

View Alarms,
Supervisories, and
Troubles

Press the

or

button to view Alarms, Supervisories, and Troubles.

Conduct a Fire Drill

1. Press ENTER to access Main Menu, then rotate the key or enter a code if prompted.
2. Press 1 to select System Tests.
3. Enter code if prompted, then press 1 to select Fire Drill.
4. Press ENTER to start the fire drill. Press ENTER to end the fire drill.

View a Point’s Status

1. Press to access Main Menu, then rotate the key or enter a code if prompted.
2. Then press 2 to select Point Functions.
3. Enter code if prompted, then press 2 to select Point Status.

4. Select the module the device is located on by using the

or

, then press ENTER.

5. Enter the point number.

Check Detector
Sensitivity

1. Follow steps 1 through 5 for viewing a point status.

2. Press Rt Arrow

to view detector sensitivity.

Set Time and Date

1. Press ENTER to access Main Menu, then rotate the key or enter a code if prompted.
2. Then press 4 to select Set Time & Date. Enter a code if prompted. Make changes in the

fields on the screen as necessary.

3. Press ENTER if you wish to keep the changes. Press ENTER to set the entered time

and date.

Enable / Disable a Point

1. Rotate the key or enter a code to access to access Main Menu.
2. Press 2 to select Point Functions.
3. Press 1 for Disable / Enable Pt
4. Press 7 for Disable / Enable Pt.

5. Use the

or

arrow or to move through the list. Then press ENTER to select the

module where the point you want to disable/enable is located

6. Enter the point or circuit number that you want to disable/enable.

7. Press Rt Arrow

to toggle between NORMAL (enable) or DISABLE.

View Event History

1. Press ENTER to access Main Menu, then rotate the key or enter a code if prompted.
2. Press 3 to select Event History.

3. Press the

or

to view events in the history buffer.

For Service Call:

Acknowledge

Mark