Before You Begin Installing

151274-L8

3-8

1. Total does not include isolator devices or accessory bases.

2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed

during that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current
that can be drawn from the panel.

3. Use next size battery with capacity greater than required.

4. SK-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. This should be considered

when determining auxiliary power capacity but not calculated into current requirements for day to day operation.

5. The SK-Duct housing contains a vacant mount for a SK-Relay (sold separately). Current draw for the SK-Relay is calculated

by increasing the SK-Relay row of the calculation sheet by one for each SK-Relay used with a SK-Duct.

6. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.

3.6.1.2 Current Draw Worksheet for SD SLC Devices

Use Table 3-3 to determine current requirements during alarm/battery standby operation when SD SLC devices are
installed. (Copy the page if additional space is required.)

Alarm: mA

mA

Alarm: mA

mA

C

Notification Appliances Current

mA

D

Total current ratings of all devices in system (line A + line B + C)

mA

mA

E

Total current ratings converted to amperes (line D x .001):

A

A

F

Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):

H

G

Multiply lines E and F.

Total standby AH

AH

H

Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)

H

I

Multiply lines E and H.

Total alarm AH

AH

J

Add lines G and I.

3

Total ampere hours required

AH

Table 3-3: Current Draw worksheet for SD Devices

Device

Number of

Devices

Current per Device

Standby

Current

Alarm

Current

For each device use this formula: This column X This column = Current per number of devices.

5808 Fire Panel (Current draw from
battery)

1

Standby: 170 mA 170 mA

Alarm: 365 mA

365 mA

Addressable SLC Devices

SD500-AIM

(127 max.)

1

Standby/Alarm: .55 mA

5

mA

mA

SD500-MIM

mA

mA

SD500-ARM

mA

mA

SD500-PS

SD505-AHS

mA

mA

SD505-AIS

mA

mA

SD505-APS

mA

mA

SD500-ANM

(127 max.)

1

Aux. Pwr

Standby: 8 mA mA

Alarm: 60 mA

mA

SLC

Standby/Alarm: 55 mA mA

mA

Table 3-2: Current Draw Worksheet for SK Devices

Device

Number

of

Devices

Current per Device

Standby

Current

Alarm

Current