Programming

151274-L8

7-16

SLC Loop

CO SMOKE
DETECTOR

ALRM CO/
ALRM FIRE

SUP CO/
ALRM FIRE

ALRM CO/
SUP FIRE

SUP CO/SUP
FIRE

Latching

Supervisory switches can be latching or non-
latching.

Non Latching

SWITCH

MAN_PULL

Use this switch type for manual pull stations.
This input is always latched. The switch can
clear only when an alarm is reset.

WATER-
FLOW

Use this switch type for monitoring water flow
in a sprinkler system. Switch closure will
cause a sprinkler alarm. Water flow switches
can be programmed as latching or non-
latching.

You can program a delay of up to 90 seconds
to be used with a water flow switch. The delay
allows for normal, brief changes in sprinkler
system water pressure. The water flow alarm
will not activate unless the switch is active for
the programmed delay time.

Note:

Waterflow delay of the FACP and

the waterflow device shall not exceed 90 sec-
onds.

If a delay is used, the system begins counting
down when the switch closes. If the switch
opens (restores) before the timer expires, a
water flow alarm is not generated. If the water
flow switch remains closed after the timer
expires, a water flow alarm will be generated.

SUPERVISY

Non Latching

Use this switch type for tamper monitoring of
sprinklers and other fire protection devices. If
a contact closes, a sprinkler supervisory
event will be generated. Supervisory switches
can be latching or non-latching.

FIREDRILL

System-level, non latching switch. This switch
is an alternative way of causing a fire drill. It
has the same operation as the fire drill option
available from the annunciator. When the
switch is activated, a fire drill begins; when
the switch is de-activated, a fire drill ends.

SILENCE

System-level switch provides an alternate
way to silence the system; same effect as
pressing the Silence key.

RESET

System-level switch provides an alternate
way to reset the system; same effect as
pressing the Reset key.

Table 7-5 Point Programming

Module Type

Type

Selection

Function

Latching

Option

Comments