SilentKnight 5808 User Manual
Page 149
IntelliKnight 5808 Installation Manual
151274-L8
9-5
Notification Trouble
Trouble
FT
1000+Group
#
1
320
00
Group #
Notification Output trouble restore
Trouble
FJ
1000+Group
#
3
320
00
Group #
Positive Alarm Sequence
acknowledge switch trouble
Trouble
FT
Zone #
1
373
00
Zone #
Positive Alarm Sequence
acknowledge switch trouble restore
Trouble
FJ
Zone #
3
373
00
Zone #
SLC LED Module trouble restore
Trouble
ER
0000
3
333
00
000
SLC LED Module trouble
Trouble
ET
0000
1
333
00
000
Status Point Types Trouble
Trouble
UT
0
1
379
00
000
Status Point Types Trouble Restore
Trouble
UJ
0
3
379
00
000
Supervisory/Tamper switch trouble
restore
Trouble
FJ
Zone #
3
373
00
Zone #
Supervisory condition restore
Trouble
FR
Zone #
3
200
00
Zone #
Supervisory condition
Trouble
FS
Zone #
1
200
00
Zone #
Supervisory/Tamper switch trouble
Trouble
FT
Zone #
1
373
00
Zone #
System-based AUX1 switch alarm
Alarm
UA
1000
1
140
01
000
System-based AUX2 switch alarm
Alarm
UA
2000
1
140
02
000
System-based AUX1 switch alarm
restore
Restore
UH
1000
3
140
01
000
System-based AUX2 switch alarm
restore
Restore
UH
2000
3
140
02
000
System-based AUX1 switch trouble
restore
Trouble
UJ
1000
3
373
01
000
System-based AUX2 switch trouble
restore
Trouble
UJ
2000
3
373
02
000
System-based AUX1 switch trouble
Trouble
UT
1000
1
373
01
000
System-based AUX2 switch trouble
Trouble
UT
2000
1
373
02
000
Voice Aux Emergency X Alarm
1
Alarm
UA
2 + Emergen-
cy #
1
170 +
Emer-
gency
#
00
002 +
Emergency #
Voice Aux Emergency X Alarm Re-
store
1
Restore
UH
2 + Emergen-
cy #
3
170 +
Emer-
gency
#
00
002 +
Emergency #
Water flow switch alarm
Alarm
SA
Zone #
1
113
00
Zone #
Water flow switch alarm restore
Restore
SH
Zone #
3
113
00
Zone #
Water flow switch trouble
Trouble
ST
Zone #
1
373
00
Zone #
Water flow switch trouble restore
Trouble
SJ
Zone #
3
373
00
Zone #
Zone-based AUX1 switch alarm
Alarm
UA
1000+ Zone # 1
140
01
Zone #
Zone-based AUX2 switch alarm
Alarm
UA
2000+ Zone # 1
140
02
Zone #
Zone-based AUX1 switch alarm
restore
Restore
UH
1000+ Zone # 3
140
01
Zone #
Zone-based AUX2 switch alarm
restore
Restore
UH
2000+ Zone # 3
140
02
Zone #
SIA Reporting Format
Contact ID Reporting Format
Event Description
Event
Family
Module
ID #
(if any)
SIA
Event
Code
Parameter (if
any)
Qualifier
Event
Code
Group
#
Contact
#