SilentKnight 5808 User Manual
Page 150

Reporting
151274-L8
9-6
Zone-based AUX1 switch trouble
restore
Trouble
UJ
1000+ Zone # 3
373
01
Zone #
Zone-based AUX2 switch trouble
restore
Trouble
UJ
2000+ Zone # 3
373
02
Zone #
Zone-based AUX1 switch trouble
Trouble
UT
1000+ Zone # 1
373
01
Zone #
Zone-based AUX2 switch trouble
Trouble
UT
2000+ Zone # 1
373
02
Zone #
Point Events
Note: Point events are reported only when “Report by Point” is selected. When
SK protocol devices are used sensors 1–99 are reported as Pnt #s 1–99, and
modules 1–99 are reported as Pnt #s 201-–299.
Auxiliary switch input disabled
Disable
pi Exp. ID
UB
Point #
1
571
Exp. ID
Point #
Auxiliary switch input re-enabled
Disable
pi Exp. ID
UU
Point #
3
571
Exp. ID
Point #
An unexpected SLC device has
been detected
Trouble
pi Exp. ID
XE
Point #
1
380
Exp. ID
Point #
An unexpected SLC device has
been removed
Trouble
pi Exp. ID
XI
Point #
3
380
Exp. ID
Point #
Auxiliary Power trouble
Trouble
pi Exp. ID
FT
Point #
1
320
Exp. ID
Point #
Aux Power trouble restore
Trouble
pi Exp. ID
FJ
Point #
3
320
Exp. ID
Point #
CO Detector Alarm
Alarm
pi Exp. ID
GA
Point #
1
162
Exp. ID
Point #
CO Detector Alarm Restore
Restore
pi Exp. ID
GH
Point #
3
162
Exp. ID
Point #
CO Detector Trouble
Trouble
pi Exp. ID
GT
Point #
1
373
Exp. ID
Point #
CO Detector Trouble Restore
Trouble
pi Exp. ID
GJ
Point #
3
373
Exp. ID
Point #
CO Supervisory Condition
Trouble
pi Exp. ID
GS
Point #
1
200
Exp. ID
Point #
CO Supervisory Condition Restore
Trouble
pi Exp. ID
GR
Point #
3
200
Exp. ID
Point #
CO Detector Input Switch Disabled
Disable
pi Exp. ID
GB
Point #
1
571
Exp. ID
Point #
CO Detector Input Switch Enabled
Disable
pi Exp. ID
GU
Point #
3
571
Exp. ID
Point #
CO Detector Disabled
Disable
pi Exp. ID
GB
Point #
1
571
Exp. ID
Point #
CO Detector Enabled
Disable
pi Exp. ID
GU
Point #
3
571
Exp. ID
Point #
Detector Alarm
Alarm
pi Exp. ID
FA
Point #
1
110
Exp. ID
Point #
Detector Alarm restore
Restore
pi Exp. ID
FH
Point #
3
110
Exp. ID
Point #
Detector Trouble
Trouble
pi Exp. ID
FT
Point #
1
373
Exp. ID
Point #
Detector Trouble restore
Trouble
pi Exp. ID
FJ
Point #
3
373
Exp. ID
Point #
Emergency Alarm # Point Alarm
1
Alarm
pi Exp. ID
QA
(EPPP) E -
Emergency #
PPP - Point #
1
220 +
Emer-
gency
#
Exp. ID
Point #
Emergency Alarm # Point Alarm Re-
store
1
Restore
pi Exp. ID
QH
(EPPP) E -
Emergency #
PPP - Point #
3
220 +
Emer-
gency
#
Exp. ID
Point #
Emergency Alarm # Point Trouble
1
Trouble
pi Exp. ID
QT
Point #
1
242
Exp. ID
Point #
Emergency Alarm # Point Trouble
Restore
1
Trouble
pi Exp. ID
QJ
Point #
3
242
Exp. ID
Point #
Emergency Alarm # Point Disabled
1
Disable
pi Exp. ID
QB
Point #
1
243
Exp. ID
Point #
Emergency Alarm # Point Enabled
1
Disable
pi Exp. ID
QU
Point #
3
243
Exp. ID
Point #
Emergency NAC Trouble
1
Trouble
pi Exp. ID
QT
Point #
1
320
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
Event Description
Event
Family
Module
ID #
(if any)
SIA
Event
Code
Parameter (if
any)
Qualifier
Event
Code
Group
#
Contact
#