beautypg.com

SilentKnight 5808 User Manual

Page 148

background image

Reporting

151274-L8

9-4

Water release circuit has been
disabled

Trouble

pi Exp. ID

SS

Point #

1

203

Exp. ID

Point #

Water release circuit has been re-
enabled

Trouble

pi Exp. ID

SR

Point #

3

203

Exp. ID

Point #

Walk test end

Test

TE

0

3

607

00

000

Walk test begin

Test

TS

0

1

607

00

000

Zone Events

Note: Zone events are reported only when “Report by Zone” is selected.

Auxiliary power trouble

Trouble

FT

0000

1

320

00

000

Auxiliary power trouble restore

Trouble

FJ

0000

3

320

00

000

CO Detector Alarm

Alarm

GA

Zone #

1

162

00

Zone #

CO Detector Alarm Restore

Restore

GH

Zone #

3

162

00

Zone #

CO Detector Trouble

Trouble

GT

Zone #

1

373

00

Zone #

CO Detector Trouble Restore

Trouble

GJ

Zone #

3

373

00

Zone #

CO Supervisory Condition

Trouble

GS

Zone #

1

200

00

Zone #

CO Supervisory Condition Restore

Trouble

GR

Zone #

3

200

00

Zone #

Detector Trouble

Trouble

FT

Zone #

1

373

00

Zone #

Detector Trouble Restore

Trouble

FJ

Zone #

3

373

00

Zone #

Detector Alarm

Alarm

FA

Zone #

1

110

00

Zone #

Detector Alarm Restore

Restore

FH

Zone #

3

110

00

Zone #

Emergency Notification Trouble

1

Trouble

QT

1000 +
Group #

1

320

00

Group #

Emergency Notification Trouble

Restored

1

Trouble

QJ

1000 +
Group #

3

320

00

Group #

Emergency Switch Trouble

1

Trouble

QT

0

1

242

00

000

Emergency Switch Trouble Restore

1

Trouble

QJ

0

3

242

00

000

External Reset/Silence/Fire Drill
switch trouble

Trouble

UT

0000

1

373

00

000

External Reset/Silence/Fire Drill
switch trouble restore

Trouble

UJ

0000

3

373

00

000

LOC Mic Activated Emergency

Alarm

1

Alarm

QA

0

1

220

00

000

LOC Mic Activated Emergency Alarm

Restore

1

Restore

QH

0

3

220

00

000

LOC/Point Emergency # Alarm

1

Alarm

QA

Emergency #

1

220 +
Emer-
gency
#

00

Emergency #

LOC/Point Emergency # Alarm Re-

store

1

Restore

QH

Emergency #

3

220 +
Emer-
gency
#

00

Emergency #

Manual Pull switch alarm

Alarm

FA

Zone #

1

115

00

Zone #

Manual Pull switch alarm restore

Restore

FH

Zone #

3

115

00

Zone #

Manual Pull switch trouble

Trouble

FT

Zone #

1

373

00

Zone #

Manual Pull switch trouble restore

Trouble

FJ

Zone #

3

373

00

Zone #

SIA Reporting Format

Contact ID Reporting Format

Event Description

Event

Family

Module

ID #

(if any)

SIA

Event

Code

Parameter (if

any)

Qualifier

Event

Code

Group

#

Contact

#