beautypg.com

4 time options, 1 water flow delay, 2 alarm verification time – SilentKnight 5808 User Manual

Page 119: 4 time options -27, N 7.6.4.2

background image

IntelliKnight 5808 Installation Manual

151274-L8

7-27

6.

Select the holiday schedules you wish to edit (1- holidays 1 - 9, 2- holidays 10 - 18).

Figure 7-18 Edit Holidays Screen

7.

Enter the month of the Holiday, then press

ENTER

.

8.

Enter the day of the month for the Holiday, then press

ENTER

.

9.

Repeat steps 6 and 7 for any remaining holidays you wish to program.

7.6.4

Time Options

Through this programming option you can set the water flow delay time, low AC report delay, Alarm
verification, AMPM/Military time and AC Frequency.

1.

Enter the installer code.

2.

Select 7 for Program Menu.

3.

Select 5 for System Options.

4.

Select 5 for Time Options.

7.6.4.1

Water Flow Delay

You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow
switch. The delay is system-wide. All water flow switches on the system will use the same delay period.

To access the screen for programming water flow delay, follow these steps:

1.

Enter the installer code.

2.

Select 7 for Program Menu.

3.

Select 5 for System Options.

4.

Select 5 for Time Options.

A screen similar to the one shown in Figure 7-19 will display.

Figure 7-19 Water Flow Delay Programming Screen

5.

Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then press

ENTER

.

7.6.4.2

Alarm Verification Time

You can set the alarm verification time from 1 to 250 seconds (default is 60 seconds).

To set the alarm verification:

Pre-programmed
Holidays

Programmable
Holiday locations

Delay in seconds
before waterflow
alarm occurs.
(00 - 90)