4 time options, 1 water flow delay, 2 alarm verification time – SilentKnight 5808 User Manual
Page 119: 4 time options -27, N 7.6.4.2

IntelliKnight 5808 Installation Manual
151274-L8
7-27
6.
Select the holiday schedules you wish to edit (1- holidays 1 - 9, 2- holidays 10 - 18).
Figure 7-18 Edit Holidays Screen
7.
Enter the month of the Holiday, then press
ENTER
.
8.
Enter the day of the month for the Holiday, then press
ENTER
.
9.
Repeat steps 6 and 7 for any remaining holidays you wish to program.
7.6.4
Time Options
Through this programming option you can set the water flow delay time, low AC report delay, Alarm
verification, AMPM/Military time and AC Frequency.
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 5 for Time Options.
7.6.4.1
Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow
switch. The delay is system-wide. All water flow switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 5 for Time Options.
A screen similar to the one shown in Figure 7-19 will display.
Figure 7-19 Water Flow Delay Programming Screen
5.
Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then press
ENTER
.
7.6.4.2
Alarm Verification Time
You can set the alarm verification time from 1 to 250 seconds (default is 60 seconds).
To set the alarm verification:
Pre-programmed
Holidays
Programmable
Holiday locations
Delay in seconds
before waterflow
alarm occurs.