SK and SD SLC Device Installation

151274-L8

5-2

5.2

List of SD SLC Devices

The following SD SLC devices can be used with the control panel. See the appropriate section number in this
manual or the device installation instructions (packaged with the device) for more information.

Note: The control panel supports the use of either SD SLC devices or SK SLC devices. You cannot install both

SLC device types on this control panel.

5.3

Maximum Number of Devices

The 5808 supports SK or SD devices on one 5808 system. The maximum number of devices per system varies
depending on device protocol. Device support is as follows:

SK Devices–A 5808 system can support a total of 99 SK detectors and 99 SK modules.

OR

SD Devices–A 5808 system can support a total of 127 SD SLC detectors and modules, in any combination.

5.4

Wiring Requirements for SLC Devices

The following information applies to all SLC devices. Refer to the section that describes the type of device you
are installing for details.

SD

Model Number

Model Name/Description

Section / Install

Sheet PN

SD505-APS

Photoelectric smoke detector.

Section 5.7

SD505-AIS

Ionization smoke detector

SD505-AHS

Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).

SD505-6AB

6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS.

150955

SD505-6IB

6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and
SD505-APS

151175

SD505-6RB

6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS

151192

SD505-6SB

6" sounder base for use with the SD505-AHS, SD505-AIS, and SD505-APS SLC
devices

151191

SD505-DUCT

Duct Smoke Detector. Duct Housing including the SD505-APS Analog Photoelectric
Smoke Sensor. Intake tubing for duct available in three lengths:

SD505-T2 (2.5 foot); SD505-T5 (5 foot); SD505-T10 (10 foot)

1700-09882

SD505-DUCTR

Duct Detector housing with relay base. Duct housing with relay base including
SD505-APS Analog Photoelectric Smoke detector pre-installed

1700-09882

SD500-PS/-PSDA

Single or dual action addressable pull station

151177

SD500-AIM

Addressable input module (switch input), standard size, DIP switch configured

151071

SD500-MIM

Mini input monitor module (switch input), small size, DIP switch configured. Fits in
single-gang box with manual pull station switch.

151071

SD500-ANM

Addressable notification module

151109

SD500ARM

Addressable relay module DIP switch configured.

151091

SD500-SDM

Addressable smoke detector module. Use to assign an address to a loop of
conventional devices.

151193

SD500-LIM

Line isolator module. Fits in a double gang box.

151125

SD500-LED

Addressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-
LED Driver Modules can be used per SLC loop.

151232

SD505-DTS-K

Remote test switch & LED indicator for the SD505-DUCTR

1700-09882