IntelliKnight 5808 Installation Manual

151274-L8

7-11

Operation with system switches.

Figure 7-9 Group Properties Screen Programming Options

Latching / Non-latching Outputs

Outputs that are programmed as Latching remain active until the system has been manually reset. Non-latching
outputs stop activating automatically when the condition clears.

Silencing Options

The following silencing options are available for each output group.

Response with System-Wide Conditions

You can select whether an output group will respond to various system-wide occurrences. (See Figure 7-9 for
location of this field).

Table 7-2: Silencing Options

Option

Description

SILENCE

Silenceable. The output group can be silenced through th

e SILENCE key.

NON-SIL

Not silenceable. The output group cannot be silenced. Activation of the

SILENCE ke

y will be ignored

for this output group.

AUT UNSIL

Auto Unsilenced. If this option is selected, the output group can be silenced for a programmed time-
frame. If the condition that caused the output to activate has not cleared during the time-frame, the
output reactivates. If you select this option, select the time-frame in the delay field. Range is 05-60
minutes. (See Figure 7-9 for location of field.)

SIL-INHIB

Timed Silence after Inhibit. If this option is selected, the output group must be audible for a
programmed number of minutes before it can be silenced. If the condition that caused the output to
activate has not cleared during the time-frame, the output can be silenced. If you select this option,
select the timeframe in the delay field. Range is 05-60 minutes. (See Figure 7-9 for location of field.)

SHUT-DOWN

If this option is selected, the output group will automatically silence (shut down) after the programmed
time period. If you select this option, select the timeframe in the delay field. Range is 05-60 minutes.
(See Figure 7-9 for location of field.)

Table 7-3: Output Group Response Choices

Option

Description

ManPull

Manual Pull Activation. Select Yes if you want this group to activate for all manual pull
alarms that occur in the system.

Note:

Even though manual pull switches are assigned to zones, activation selected

here for manual pull will override zone-programmed activation.