IntelliKnight 5808 Installation Manual

151274-L8

7-9

7.3.1.5

Zone Accessory Options

This option applies to detectors that are used with Sounder bases or Relay bases.

Fire Cadence_ _/ CO Cadence_ _ (choose from Patterns 00 to 23).

Note: The B200S Sounder bases is intended to be used along with the CO cadence setting.

Local Zone (choose Y or N, for Yes or No).

7.3.2

Add Zone

To add a zone, follow these steps:

1.

Enter the installer code.

2.

Select 7 for Program Menu.

3.

Press 2 to enter zone menu.

4.

Press 2 to add a zone.

A zone will be added. The system will assign the next available zone number. Options for this zone can now
be programmed through the Zone Edit sub-menu. Up to 125 zones can be used.

7.3.3

Delete Zone

To delete a zone, follow these steps:

1.

Enter the installer code.

2.

Select 7 for Program Menu.

3.

Press 2 to enter zone menu.

4.

Press 3 to delete a zone.

5.

Select a zone to delete.

A warning screen will display. If you want to proceed with deleting the zone, select Yes. To cancel, select
No.

7.3.4

View Zone Points

To view the points in a zone, follow these steps:

1.

Enter the installer code.

2.

Select 7 for Program Menu.

3.

Press 2 to enter zone menu.

4.

Press 4 to view zone points.

5.

Enter the number of the zone you wish to view, then press

ENTER

.

Figure 7-7 View Zone Points Screen

Zone Number

Module or

Device Address

Point Number

Total Number of
Points in the Zone