SD500-LED
(40 max.)
1
Aux. Pwr
Standby: 10 mA mA
Alarm: 220 mA
mA
LED: 10 mA mA
mA
SLC
Standby/Alarm: .55 mA mA
mA
SD500-SDM
(127 max.)
1
SLC
Standby/Alarm: .55 mA mA
mA
Aux. Pwr
Standby: 20 mA mA
Alarm: 106 mA
mA
SLC Accessory Bases
SD505-6RB
(127 max.)
Standby/Alarm: .082 mA mA
mA
SD505-6SB
(127 max.)
Aux. Pwr
Standby: 1 mA mA
Alarm: 32 mA
mA
SLC
Standby/Alarm: .082 mA mA
mA
SD505-DUCTR
(127 max.)
Aux. Pwr
Standby: 20 mA
2
mA
Alarm: 62 mA
2
mA
SLC
Standby/Alarm: .5 mA mA
mA
SD505-DTS-K
(127 max.)
None, included with SD505-DUCTR worst case.
SD505-DUCT
(127 max.)
SLC
Standby/Alarm: .5 mA mA
mA
SLC Isolator Devices
SD500-LIM
(254 max.)
Standby/Alarm: .092 mA mA
mA
SD505-6IB
(127 max.)
Accessories Modules
5860 Remote Fire Alarm
Annunciator
(12 max.)
Standby: 20 mA mA
Alarm: 65 mA
mA
5824 Serial/Parallel Printer
Interface
(2 max.)
Standby/Alarm: 45 mA mA
mA
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.)
Standby: 35 mA mA
Alarm: 145 mA
mA
5865-3 LED Annunciator
Standby: 35 mA mA
Alarm: 145 mA
mA
5880 LED I/O Module
Standby: 35 mA mA
Alarm: 200 mA
mA
5883 Relay Interface
(32 max.)
Standby: 0 mA mA
Alarm: 220 mA
(22 mA per relay)
mA
5496 Notification Power Expander
(8 max.)
Standby/Alarm: 10 mA mA
mA
5895XL Intelligent Power Expander
Standby/Alarm: 10 mA mA
mA
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.)
Standby: 35 mA mA
Alarm: 145 mA
mA
A
Total System Current
Auxiliary Devices
3
Refer to devices manual for current rating.
Alarm/Standby: mA mA
mA
Alarm/Standby: mA mA
mA
Alarm/Standby: mA mA
mA
B
Auxiliary Devices Current
Table 3-3: Current Draw worksheet for SD Devices
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current